Skip to main content
Skip table of contents

Conformance Statement

WARNING!

Changing the parameters regarding the configuration of the transmission will only take effect after restarting the unit (except for the registers the value of which is read from the switch).

Conformance Statement Regarding Implementation of BACnet Protocol

Date

2020-09-04

Vendor Name

iSMA CONTROLLI S.p.A

Product Name

iSMA-B-MIX

iSMA-B-MINI

iSMA-B-MAX

Product Model Number

iSMA-B-MIX18

iSMA-B-MIX38

iSMA-B-8I

iSMA-B-8U

iSMA-B-4O-H

iSMA-B-4I4O-H

iSMA-B-4U4O-H

iSMA-B-4U4A-H

iSMA-B-4TO-H

iSMA-B-MIX18-IP

iSMA-B-MIX38-IP

iSMA-B-8I-IP

iSMA-B-8U-IP

iSMA-B-4O-H-IP

iSMA-B-4I4O-H-IP

iSMA-B-4U4O-H-IP

iSMA-B-4U4A-H-IP

iSMA-B-4TO-H-IP

iSMA-B-12O-H

iSMA-B-12O-H-IP

iSMA-B-24I

iSMA-B-24-IP

Firmware Revision

7.0

BACnet Protocol Revision

1.14

The conformance statement regarding the implentation of the BACnet protocol

BACnet Standardized Device Profile

All I/O modules have been standardized as the BACnet Smart Sensors (B-SS).

Supported BACnet Interoperability Building Blocks

Application Service (B-SS)

Designation

Data Sharing - Read Property – B

DS-RP-B

Data Sharing - Write Property - B

DS-WP-B

Data Sharing - COV - B

DS-COV-B

Device Management - Dynamic Device Binding - B

DM-DDB-B

Device Management - Dynamic Object Binding - B

DM-DOB-B

Data Sharing - Read Property Multiple – B

DS-RPM-B

Data Sharing - Write Property Multiple – B

DS-WPM-B

Supported building blocks

Supported BACnet Standard Object Types

The following is a list of the standard object types as defined by ASHRAE.

Object Name

Object Numbers for a different type of modules

8U, 8U-IP

8I, 8I-IP

4I4O-H, 4I4O-H-IP

4U4O-H, 4U4O-H-IP

4U4A-H, 4U4A-H-IP

4O-H, 4O-H-IP

4TO-H, 4TO-H-IP

MIX18, MIX18-IP

MIX38, MIX38-IP

12O-H, 12O-H-IP24I, 24I-IP

Analog Input

8



4

4



5

8



Analog Output





4


4

4

6



Analog Value

9

9

10

18

10

2

2

12

22

225

Binary Input


8

4





5

12


24

Binary Output



4

4


4

4

4

12

12

Binary Value

8


8

12

4



5

8



Multistate Value

16


8

16

16

4

8

14

22

12

Accumulator


8

4





5

12


24

Device

1

1

1

1

1

1

1

1

1

11
Types of objects supported by modules

Data Link Layer Option

  • Master-Slave/Token-Passing (MS/TP) master (Clause 9), baud rates: 2400, 4800, 9600, 19200, 38400, 57600, 76800, and 115200;
  • MS/TP slave (Clause 9), baud rates: 2400, 4800, 9600, 19200, 38400, 57600, 76800, and 115200;
  • BACnet Internet Protocol (IP) (Annex J);
  • BACnet IP (Annex J), Foreign Device.

Supported Character Sets

ANSI X3.4

Supported Application Services

Application Service

Initiates Requests

Executes Requests

I-Am

Yes


I-Have

Yes


ReadProperty


Yes

ReadPropertyMultiple


Yes

Who-Has


Yes

Who-Is


Yes

WriteProperty


Yes

WritePropertyMultiple


Yes

Supported application services

About COV

All MIX, MINI, and MAX I/O modules support COV (change of value) policy. It means that the module can send a value every time it is changed. COV only works with BI, BO, AI, and AO objects. For Binary Input and Binary Output objects, the values are sent with every change. Analog Input and Analog Output objects have special COV Increment property, which defines additional sending criteria–object’s value is sent if it is changed by the COV increment value.