Skip to main content
Skip table of contents

Technical Specification

Control Point

Control Point VAV

Power Supply

DC

20-34 V

AC

24 V ± 20%

Power consumption

0.6 W at 24 V DC - panels without CO2 sensor

0.9 W at 24 V DC - panels with CO2 sensor

1.8 VA at 24 V AC - panels without CO2 sensor

2.5 VA at 24 V AC - panels with CO2 sensor

Built-in Sensors

Temperature sensor

10k NTC type, range: 0-50˚C, accuracy: ± 0.5˚C, resolution: ± 0.1˚C

Humidity sensor

(applies to versions with humidity sensor)

Range: 0-100% RH, accuracy: ± 2% RH in range of 10-90% RH, resolution: ± 1% RH

CO2 sensor

(applies to versions with CO2 sensor)

Range: 400-2000 ppm, accuracy: 50 ppm + 5% of reading

COM1

RS485 interface

Up to 128 devices

Half-duplex

Communication protocols

Modbus RTU/ASCII, BACnet MS/TP

Ports

2 RJ45, screw connector

Baud rate

2400-115200

USB

Type

USB type C

Power supply

5 V DC

Front Panel

Display

LCD 2.6"

Buttons

4 buttons (fan, up +, down -, occupancy)

4 buttons (menu, up +, down -, confirmation)

Ingress Protection

IP rating

IP20 for indoor installation

Temperature

Operating

From 0°C to +50°C (32°F to 122°F)

Storage

From -40°C to 85°C (-40°F to 185°F)

Humidity

Relative

From 5% to 95% RH (without condensation)

Screw Connector

Type

Removable screw terminals

Maximum cable size

1.5 mm2 (26…16 AWG)

Housing

Material

PC/ABS

Mounting

  • Flush wall box 60 mm

  • US 1-gang electrical outlet box

Dimensions

Width

86.30 mm/3.40 in

Length

129.30 mm/5.10 in

Height

24.80 mm/0.98 in