CO2Sensor
Warning!
Component applicable for the LP, Touch Point, and Control Point panels.
The CO2Sensor component is responsible for reading values and configuration of the CO2 sensor.

CO2Sensor component
The CO2Sensor component has the following slots:
Status: shows the component’s status;
Fault Cause: shows the fault cause description;
Fault Status: informs about the point error status (true: point read/write error);
Enable: enables or disables the component (true: enabled, false: disabled);
Poll Frequency: allows to set the reading poll frequency (fast, normal, slow);
Out: the CO2 sensor value;
Display Name: allows to set the CO2 sensor name on the display (up to 4 characters, only ASCII characters, only for the LP panel);
Visibility: activates or inactivates the sensor value on the display;
Sensor Offset: sets the CO2 sensor offset value;
Sensor Filter: sets the CO2 sensor reading filter time in seconds;
Config Trigger: sends configuration parameters to the device components on rising edge (Display Name, Visibility, Sensor Offset, Sensor Filter).
The LpCO2Sensor component has the following right-click menu actions:
Read: reads the remote device CO2 sensor value and updates the Out slot;
Read Config: reads configuration parameters from the panel (Display Name, Visibility, Sensor Offset, Sensor Filter);
Write Config: writes configuration parameters to the panel (Display Name, Visibility, Sensor Offset, Sensor Filter).