Modbus Address |
Decimal Address |
Hex |
Register Name |
Access |
Default Value |
Value Range |
Description |
|---|---|---|---|---|---|---|---|
|
40001 |
0 |
0x00 |
VERSION_TYPE |
Read/write |
|
|
Shows a firmware version and type of the panel and enables 1 of 4 available actions (reset device, reload settings, reset settings, enter bootloader) |
|
30002 |
1 |
0x01 |
ADDRESS_ROTARY_SWITCH |
Read-only |
|
0-9 |
Address set on a rotary switch |
|
30003 |
2 |
0x02 |
PROTOCOL_DIPSWITCH |
Read-only |
|
0-1 |
Protocol set on a DIP switch |
|
30004 |
3 |
0x03 |
RECEIVED_FRAMES_COUNTER |
Read-only |
0 |
|
The number of received Modbus frames reset at the start of the panel and at the change of transmission parameters |
|
30006 |
5 |
0x05 |
ERROR_FRAMES_COUNTER |
Read-only |
0 |
|
The number of received error Modbus frames reset at the start of the panel and at the change of transmission parameters |
|
30008 |
7 |
0x07 |
TRANSMITTED_FRAME_COUNTER |
Read-only |
0 |
|
The number of transmitted Modbus frames reset at the start of the panel and at the change of transmission parameters |
|
30012 |
11 |
0x0B |
LIVE_TIME |
Read-only |
|
|
Uptime of the panel in seconds |
|
40015 |
14 |
0x0E |
BACNET_DEVICE_ID |
Read/write |
0xFFFFFFFF |
|
Device's BACnet ID |
|
40017 |
16 |
0x10 |
BAUD_RATE |
Read/write |
11520 |
|
Sets the baud rate |
|
40018 |
17 |
0x11 |
STOP_BITS |
Read/write |
1 |
1-2 |
Sets the number of stop bits |
|
40019 |
18 |
0x12 |
DATA_BITS |
Read/write |
8 |
7-8 |
Sets the number of data bits (Modbus ASCII requires 7 bits) |
|
40020 |
19 |
0x13 |
PARITY_BIT |
Read/write |
0 |
0-2 |
Determines the parity bit |
|
40021 |
20 |
0x14 |
REPLY_DELAY |
Read/write |
0 |
|
Sets the delay time in ms before sending response |
|
40023 |
22 |
0x16 |
ADDRESS |
Read/write |
1 |
|
Modbus address of the device |
|
40024 |
23 |
0x17 |
PROTOCOL |
Read/write |
0 |
0-2 |
Sets the type of Modbus protocol (Modbus RTU (0), Modbus ASCII (1)) |
|
30029 |
28 |
0x1C |
SENSORS |
Read-only |
|
|
Informs about built-in sensors |
|
30201 |
200 |
0xC8 |
BACKLIGHT_LCD |
Read-only |
|
|
Actual display illumination value |
|
30202 |
201 |
0xC9 |
BACKLIGHT_KEYPAD |
Read-only |
|
|
Actual keypad illumination value |
|
40205 |
204 |
0xCC |
DEVICE_CONFIGURATION |
Read/write |
105 |
|
|
|
Bit |
Name |
0 |
1 |
|
|||
|
0 |
BUZZER |
Not active |
Active (def) |
Activates/inactivates a buzzer |
|||
|
3 |
BACKLIGHT_LCD |
Not active |
Active (def) |
Switches on/off display's backlight |
|||
|
4 |
BACKLIGHT_KEYPAD |
Not active |
Active (def) |
Switches on/off keypad's backlight |
|||
|
5 |
CO2_ALARM_LCD |
Not active |
Active |
Shows CO2 alarm on a display |
|||
|
6 |
CO2_ALARM_BUZZER |
Not active |
Active |
Switches on/off CO2 alarm's buzzer on alarm |
|||
|
8 |
CO2_ALARM_CONFIRM |
Not active |
Active (def) |
Switches on/off CO2 alarm confirmation by any button |
|||
|
11 |
PANEL_OFF |
Panel on (def) |
Panel off |
Switches on/off the panel |
|||
|
12 |
KEYPAD_OFF |
Keypad on (def) |
Keypad off |
Switches on/off the keypad |
|||
|
40207 |
206 |
0xCE |
BACKLIGHT_LCD_ACTIVE |
Read/write |
60 |
|
Contains a value of the LCD display illumination in the active mode (expressed in %) |
|
40208 |
207 |
0xCF |
BACKLIGHT_LCD_IDLE |
Read/write |
40 |
|
Contains a value of the LCD display illumination in the idle mode (expressed in %) |
|
40209 |
208 |
0xD0 |
BACKLIGHT_LCD_STANDBY |
Read/write |
0 |
|
Contains a value of the LCD display illumination in the standby mode (expressed in %) |
|
40210 |
209 |
0xD1 |
BACKLIGHT_LCD_TIME_TO_IDLE |
Read/write |
10 |
|
Sets the time, after which the LCD display goes from the active mode to idle (expressed in seconds) |
|
40211 |
210 |
0xD2 |
BACKLIGHT_LCD_TIME_TO_STANDBY |
Read/write |
5 |
|
Sets the time, after which the LCD display goes from the idle mode to standby (expressed in seconds) |
|
40212 |
211 |
0xD3 |
BACKLIGHT_KEYPAD_ACTIVE |
Read/write |
10 |
|
Contains a value of the keypad illumination in the active mode (expressed in %) |
|
40213 |
212 |
0xD4 |
BACKLIGHT_KEYPAD_IDLE |
Read/write |
40 |
|
Contains a value of the keypad illumination in the idle mode (expressed in %) |
|
40214 |
213 |
0xD5 |
BACKLIGHT_KEYPAD_STANDBY |
Read/write |
60 |
|
Contains a value of the keypad illumination in the standby mode (expressed in %) |
|
40215 |
214 |
0xD6 |
BACKLIGHT_KEYPAD_TIME_TO_IDLE |
Read/write |
10 |
|
Sets the time, after which the keypad goes from the active mode to idle (expressed in seconds) |
|
40216 |
215 |
0xD7 |
BACKLIGHT_KEYPAD_TIME_TO_STANDBY |
Read/write |
5 |
|
Sets the time, after which the keypad goes from the idle mode to standby (expressed in seconds) |
|
40217 |
216 |
0xD8 |
REFRESH_TIME |
|
5 |
1-60 |
Sets the duration of the display time of particular parameters |
|
40219 |
218 |
0xDA |
ICON_DISPLAY |
Read/write |
|
|
|
|
Bit |
Name |
0 |
1 |
|
|||
|
8 |
ECO |
Not active |
Active |
Switches on/off an ECO LED |
|||
|
40226 |
225 |
0xE1 |
CO2_SETPOINT_FOR_ALARM |
Read/write |
1500 |
|
CO2 alarm setpoint |
|
40227 |
226 |
0xE2 |
CO2_HYSTERESIS_FOR_ALARM |
Read/write |
100 |
|
CO2 alarm hysteresis |
|
30230 |
229 |
0xE5 |
ALARM_STATUS |
Read-only |
|
|
CO2 current alarm status |
|
30231 |
230 |
0xE6 |
NAVIGATIONAL_LED_MODE |
Read/write |
1 |
0-4 |
Sets a mode of the navigational LED |
|
Bit |
Name |
0 |
1 |
|
|||
|
0 |
OFF |
Not active |
Active |
|
|||
|
1 |
ON (default) |
Not active |
Active |
|
|||
|
2 |
Active on IDLE and STANDBY |
Not active |
Active |
|
|||
|
3 |
Active on IDLE only |
Not active |
Active |
|
|||
|
4 |
Active on STANDBY only |
Not active |
Active |
|
|||
|
30232 |
231 |
0xE7 |
NAVIGATIONAL_LED_BRIGHTNESS |
Read/write |
100 |
0-100 |
Navigational LED brightness |
|
30233 |
232 |
0xE8 |
NAVIGATIONAL_LED_RED |
Read/write |
100 |
0-100 |
Navigational LED color - red component intensity |
|
30234 |
233 |
0xE9 |
NAVIGATIONAL_LED_GREEN |
Read/write |
100 |
0-100 |
Navigational LED color - green component intensity |
|
30235 |
234 |
0xE10 |
NAVIGATIONAL_LED_BLUE |
Read/write |
100 |
0-100 |
Navigational LED color - blue component intensity |
|
30301 |
300 |
0x12C |
TEMPERATURE_SENSOR |
Read-only |
|
|
Actual temperature sensor value with offset |
|
30302 |
301 |
0x12D |
HUMIDITY_SENSOR |
Read-only |
|
|
Actual humidity sensor value with offset |
|
30303 |
302 |
0x12E |
CO2_SENSOR |
Read-only |
|
|
Actual CO2 sensor value with offset |
|
40304 |
303 |
0x12F |
TEMPERATURE_SENSOR_OFFSET |
Read/write |
0 |
|
Temperature sensor offset |
|
40305 |
304 |
0x130 |
HUMIDITY_SENSOR_OFFSET |
Read/write |
0 |
|
Humidity sensor offset |
|
40306 |
305 |
0x131 |
CO2_SENSOR_OFFSET |
Read/write |
0 |
|
CO2 sensor offset |
|
40307 |
306 |
0x132 |
TEMPERATURE_FILTER |
Read/write |
60 |
|
Filtering time for the temperature sensor (seconds) |
|
40308 |
307 |
0x133 |
HUMIDITY_FILTER |
Read/write |
60 |
|
Filtering time for the humidity sensor (seconds) |
|
40309 |
308 |
0x134 |
CO2_FILTER |
Read/write |
60 |
|
Filtering time for the CO2 sensor (seconds) |
|
40316 |
315 |
0x13B |
TEMPERATURE_CONFIGURATION |
Read/write |
17 |
|
|
|
Bit |
Name |
0 |
1 |
|
|||
|
0 |
ACTIVE |
Not active |
Active (def) |
Activates/deactivates the sensor |
|||
|
4 |
THIRD_POINT-ACTIVE |
No decimal |
Decimal (def) |
Sets decimal places |
|||
|
40317 |
316 |
0x13C |
HUMIDITY_CONFIGURATION |
Read/write |
17 |
|
|
|
Bit |
Name |
0 |
1 |
|
|||
|
0 |
ACTIVE |
Not active |
Active (def) |
Activates/deactivates the sensor |
|||
|
4 |
THIRD_POINT-ACTIVE |
No decimal |
Decimal (def) |
Sets decimal places |
|||
|
40318 |
317 |
0x13D |
CO2_CONFIGURATION |
Read/write |
1 |
|
|
|
Bit |
Name |
0 |
1 |
|
|||
|
0 |
ACTIVE |
Not active |
Active |
Activates/deactivates the sensor |
|||
|
40323 |
322 |
0x142 |
BUZZER_VOLUME |
Read/write |
50 |
0-100 |
Buzzer volume (%) |
|
40324 |
323 |
0x143 |
BUZZER_FREQUENCY |
Read/write |
400 |
20-20000 |
Buzzer frequency (Hz) |
|
31301 |
1300 |
0x514 |
FLASH_DEVICE_TYPE |
Read-only |
|
|
Version and type of device |
|
31302 |
1301 |
0x515 |
FLASH_HW_VERSION |
Read-only |
|
|
HW version |
|
31303 |
1302 |
0x516 |
FLASH_BOOT_VERSION |
Read-only |
|
|
Bootloader version |
|
31304 |
1303 |
0x517 |
FW_VERSION |
Read-only |
|
|
FW version separated from the VERSION_TYPE register |
|
31305 |
1304 |
0x518 |
FLASH_SERIAL_NUMBER_1 |
Read-only |
|
|
Serial number |
|
31306 |
1305 |
0x519 |
FLASH_SERIAL_NUMBER_2 |
Read-only |
|
|
Serial number |
|
31307 |
1306 |
0x51A |
FLASH_SERIAL_NUMBER_3 |
Read-only |
|
|
Serial number |
|
31308 |
1307 |
0x51B |
FLASH_SERIAL_NUMBER_4 |
Read-only |
|
|
Serial number |
|
41501 |
1500 |
0x5DC |
SETPOINT_VALUE |
Read/write |
|
0-500 |
Temperature setpoint value |
|
41502 |
1501 |
0x5DD |
EFFECTIVE_SETPOINT |
Read-only |
|
|
Sum of setpoint and offset values |
|
41503 |
1502 |
0x5DE |
DEFAULT_SETPOINT |
Read/write |
210 |
0-500 |
Default temperature setpoint |
|
41504 |
1503 |
0x5DF |
OFFSET_SETPOINT |
Read/write |
0 |
0-500 |
Temperature offset for setpoint |
|
41505 |
1504 |
0x5E0 |
SETPOINT_LOW_LIMIT |
Read/write |
180 |
|
Min. available setpoint value |
|
41506 |
1505 |
0x5E1 |
SETPOINT_HIGH_LIMIT |
Read/write |
240 |
|
Max. available setpoint value |
|
41507 |
1506 |
0x5E2 |
OFFSET_RANGE |
Read/write |
30 |
0-500 |
Limit offset value |
|
41508 |
1507 |
0x5E3 |
SETPOINT_STEP |
Read/write |
10 |
|
Setpoint step value |
|
41513 |
1512 |
0x5E8 |
SETPOINT_CONFIGURATION |
Read/write |
31 |
|
Setpoint configuration of parameters: Visible, Editable, Operating mode, Setpoint display, ThirdPointActive |
|
Bit |
Name |
0 |
1 |
|
|||
|
0 |
VISIBLE |
Not visible |
Visible (def) |
Switches on/off a temperature setpoint visibility on a display |
|||
|
1 |
EDITABLE |
Not editable |
Editable (def) |
Activates/inactivates editing of a temperature setpoint locally on the panel |
|||
|
2 |
OPERATING_MODE |
Changing offset |
Changing setpoint (def) |
Switches between changing offset or setpoint |
|||
|
3 |
SETPOINT_DISPLAY |
Show/change offset |
Show/change effective setpoint (def) |
Switches between changing offset or setpoint |
|||
|
4 |
THIRD_POINT_ACTIVE |
No decimal |
Decimal (def) |
Activates/inactivates decimal points |
|||
|
41601 |
1600 |
0x640 |
FAN_CURRENT_SPEED |
Read/write |
0 |
|
Fan speed |
|
41602 |
1601 |
0x641 |
FAN_MODE |
Read/write |
1 |
|
Fan mode |
|
41603 |
1602 |
0x642 |
FAN_TYPE |
Read/write |
|
|
Fan type |
|
41614 |
1613 |
0x64D |
FAN_CONFIGURATION |
Read/write |
2 |
|
|
|
Bit |
Name |
0 |
1 |
|
|||
|
1 |
EDITABLE |
Not editable |
Editable (def) |
Switches on/off editing fan modes locally |
|||
|
2 |
PART_EDITABLE |
Fully editable |
Auto_Off_Mode |
Switches editability of fan modes |
|||
|
6 |
FAN_CONFIG_LOCAL_MODE |
BMS (def) |
Local |
Switches between BMS/local modes |
|||
|
41701 |
1700 |
0x6A4 |
OCCUPANCY_CURRENT_STATUS |
Read/write |
|
|
Occupancy status |
|
41702 |
1701 |
0x6A5 |
OCCUPANCY_MODE |
Read/write |
|
|
Occupancy mode |
|
41707 |
1706 |
0x6AA |
OCCUPANCY_CONFIGURATION |
Read/write |
2 |
|
|
|
Bit |
Name |
0 |
1 |
|
|||
|
1 |
EDITABLE |
Not editable |
Editable (def) |
Switches on/off editing occupancy statues locally |
|||
|
6 |
OCCUPIED_CONFIG_LOCAL_MODE |
BMS (def) |
Local |
Switches between BMS/local modes |
|||
List of Modbus registers