BACnet Type & ID |
BACnet Property |
Decimal Address |
Hex |
Object Name |
Access |
Default Value |
Value Range |
Description |
|---|---|---|---|---|---|---|---|---|
|
Device |
3030 |
0 |
0x00 |
VERSION_TYPE |
Read/write |
|
|
Shows version and type of the panel and enables 1 of 4 available actions |
|
Device |
5101 |
3 |
0x03 |
RECEIVED_FRAMES_COUNTER |
Read-only |
0 |
|
The number of received Modbus frames reset at the start of the panel and at the change of transmission parameters |
|
Device |
5103 |
5 |
0x05 |
ERROR_FRAMES_COUNTER |
Read-only |
0 |
|
The number of received error Modbus frames reset at the start of the panel and at the change of transmission parameters |
|
Device |
5104 |
7 |
0x07 |
TRANSMITTED_FRAME_COUNTER |
Read-only |
0 |
|
The number of transmitted Modbus frames reset at the start of the panel and at the change of transmission parameters |
|
AI0 |
Present Value |
11 |
0x0B |
LIVE_TIME |
Read-only |
|
|
Uptime of the panel in seconds |
|
Device |
Object Identifier |
14 |
0x0E |
BACNET_DEVICE_ID |
Read/write |
0xFFFFFFFF |
|
Device's BACnet ID |
|
Device |
3084 |
16 |
0x10 |
BAUD_RATE |
Read/write |
11520 |
|
Sets the baud rate |
|
MSI1 |
Present Value |
28 |
0x1C |
SENSORS |
Read-only |
|
|
Informs about built-in sensors |
|
AI1 |
Present Value |
200 |
0xC8 |
BACKLIGHT_LCD |
Read-only |
|
|
Actual display illumination value |
|
AI2 |
Present Value |
201 |
0xC9 |
BACKLIGHT_KEYPAD |
Read-only |
|
|
Actual keypad illumination value |
|
|
|
204 |
0xCC |
DEVICE_CONFIGURATION |
Read/write |
|
|
|
|
BO0 |
Present Value |
|
|
BUZZER_ACTIVE |
|
1 |
|
Activates (1) or deactivates (0) a buzzer |
|
BO3 |
Present Value |
|
|
LCD_BACKLIGHT_ACTIVE |
|
1 |
|
Switches the LCD background illumination on (1) |
|
BO4 |
Present Value |
|
|
KEYPAD_BACKLIGHT_ACTIVE |
|
1 |
|
Switches the keypad background illumination on (1) |
|
BO5 |
Present Value |
|
|
CO2_ALARM_LCD |
|
|
|
Switches on the function of LCD background illumination flashing when CO2 alarm occurs |
|
BO6 |
Present Value |
|
|
CO2_ALARM_BUZZER |
|
|
|
Switches on a buzzer when the CO2 alarm occurs |
|
BO63 |
Present Value |
|
|
CO2_ALARM_CONFIRM |
|
1 |
|
Allows to enable confirmation of the CO2 alarm with any button of the panel |
|
BO11 |
Present Value |
|
|
PANEL_OFF |
|
0 |
|
Switches the panel off (1) |
|
BO12 |
Present Value |
|
|
KEYPAD_OFF |
|
0 |
|
Switches the panel keypad off (1) |
|
AO3 |
Present Value |
206 |
0xCE |
BACKLIGHT_LCD_ACTIVE |
Read/write |
60 |
|
Contains a value of the LCD display illumination in the active mode (expressed in %) |
|
AO4 |
Present Value |
207 |
0xCF |
BACKLIGHT_LCD_IDLE |
Read/write |
40 |
|
Contains a value of the LCD display illumination in the idle mode (expressed in %) |
|
AO5 |
Present Value |
208 |
0xD0 |
BACKLIGHT_LCD_STANDBY |
Read/write |
0 |
|
Contains a value of the LCD display illumination in the standby mode (expressed in %) |
|
AO6 |
Present Value |
209 |
0xD1 |
BACKLIGHT_LCD_TIME_TO_IDLE |
Read/write |
10 |
|
Sets the time after which the LCD display goes from the active mode to idle (expressed in seconds) |
|
AO7 |
Present Value |
210 |
0xD2 |
BACKLIGHT_LCD_TIME_TO_STANDBY |
Read/write |
5 |
|
Sets the time after which the LCD display goes from the idle mode to standby (expressed in seconds) |
|
AO8 |
Present Value |
211 |
0xD3 |
BACKLIGHT_KEYPAD_ACTIVE |
Read/write |
10 |
|
Contains a value of the keypad illumination in the active mode (expressed in %) |
|
AO9 |
Present Value |
212 |
0xD4 |
BACKLIGHT_KEYPAD_IDLE |
Read/write |
40 |
|
Contains a value of the keypad illumination in the idle mode (expressed in %) |
|
AO10 |
Present Value |
213 |
0xD5 |
BACKLIGHT_KEYPAD_STANDBY |
Read/write |
60 |
|
Contains a value of the keypad illumination in the standby mode (expressed in %) |
|
AO11 |
Present Value |
214 |
0xD6 |
BACKLIGHT_KEYPAD_TIME_TO_IDLE |
Read/write |
10 |
|
Sets the time after which the keypad goes from the active mode to idle (expressed in seconds) |
|
AO12 |
Present Value |
215 |
0xD7 |
BACKLIGHT_KEYPAD_TIME_TO_STANDBY |
Read/write |
5 |
|
Sets the time after which the keypad goes from the idle mode to standby (expressed in seconds) |
|
AO13 |
Present Value |
216 |
0xD8 |
REFRESH_TIME |
|
5 |
1-60 |
Sets the duration of the display time of particular parameters |
|
|
|
218 |
0xDA |
ICON_DISPLAY |
Read/write |
|
|
|
|
BO22 |
Present Value |
|
|
ECO |
|
|
|
Switches on an ECO LED |
|
AO17 |
Present Value |
223 |
0xDF |
EXIT_EDIT_TIME |
Read/write |
|
|
Sets the time after which edition of any editable parameter is finished |
|
AO19 |
Present Value |
225 |
0xE1 |
CO2_SETPOINT_FOR_ALARM |
Read/write |
1500 |
|
CO2 alarm setpoint |
|
AO20 |
Present Value |
226 |
0xE2 |
CO2_HYSTERESIS_FOR_ALARM |
Read/write |
100 |
|
CO2 alarm hysteresis |
|
BI0 |
Present Value |
229 |
0xE5 |
ALARM_STATUS |
Read-only |
|
|
CO2 current alarm status |
|
MSV5 |
Present Value |
230 |
0xE6 |
NAVIGATIONAL_LED_MODE |
Read/write |
1 |
0-4 |
Sets a mode of the navigational LED |
|
AO22 |
Present Value |
231 |
0xE7 |
NAVIGATIONAL_LED_BRIGHTNESS |
Read/write |
100 |
0-100 |
Navigational LED brightness |
|
AO23 |
Present Value |
232 |
0xE8 |
NAVIGATIONAL_LED_RED |
Read/write |
100 |
0-100 |
Navigational LED color - red component intensity |
|
AO24 |
Present Value |
233 |
0xE9 |
NAVIGATIONAL_LED_GREEN |
Read/write |
100 |
0-100 |
Navigational LED color - green component intensity |
|
AO25 |
Present Value |
234 |
0xE10 |
NAVIGATIONAL_LED_BLUE |
Read/write |
100 |
0-100 |
Navigational LED color - blue component intensity |
|
AI4 |
Present Value |
300 |
0x12C |
TEMPERATURE_SENSOR |
Read-only |
|
|
Actual temperature sensor value with offset |
|
AI5 |
Present Value |
301 |
0x12D |
HUMIDITY_SENSOR |
Read-only |
|
|
Actual humidity sensor value with offset |
|
AI6 |
Present Value |
302 |
0x12E |
CO2_SENSOR |
Read-only |
|
|
Actual CO2 sensor value with offset |
|
AI4 |
4205 |
303 |
0x12F |
TEMPERATURE_SENSOR_OFFSET |
Read/write |
0 |
|
Temperature sensor offset |
|
AI5 |
4205 |
304 |
0x130 |
HUMIDITY_SENSOR_OFFSET |
Read/write |
0 |
|
Humidity sensor offset |
|
AI6 |
4205 |
305 |
0x131 |
CO2_SENSOR_OFFSET |
Read/write |
0 |
|
CO2 sensor offset |
|
AI4 |
4003 |
306 |
0x132 |
TEMPERATURE_FILTER |
Read/write |
60 |
|
Filtering time for the temperature sensor (seconds) |
|
AI5 |
4003 |
307 |
0x133 |
HUMIDITY_FILTER |
Read/write |
60 |
|
Filtering time for the humidity sensor (seconds) |
|
AI6 |
4003 |
308 |
0x134 |
CO2_FILTER |
Read/write |
60 |
|
Filtering time for the CO2 sensor (seconds) |
|
|
|
315 |
0x13B |
TEMPERATURE_CONFIGURATION |
Read/write |
|
|
|
|
AI4 |
Out Of Service |
|
|
ACTIVE |
|
1 |
|
Activates/deactivates the sensor |
|
AI4 |
4202 |
|
|
THIRD_POINT_ACTIVE |
|
|
|
Sets decimal places |
|
|
|
316 |
0x13C |
HUMIDITY_CONFIGURATION |
Read/write |
|
|
|
|
AI5 |
Out Of Service |
|
|
ACTIVE |
|
1 |
|
Activates/deactivates the sensor |
|
AI5 |
4202 |
|
|
THIRD_POINT_ACTIVE |
|
|
|
Sets decimal places |
|
|
|
317 |
0x13D |
CO2_CONFIGURATION |
Read/write |
|
|
|
|
AI6 |
Out Of Service |
|
|
ACTIVE |
|
1 |
|
Activates/deactivates the sensor |
|
AO27 |
Present Value |
322 |
0x142 |
BUZZER_VOLUME |
Read/write |
50 |
0-100 |
Buzzer volume (%) |
|
AO28 |
Present Value |
323 |
0x143 |
BUZZER_FREQUENCY |
Read/write |
400 |
20-20000 |
Buzzer frequency (Hz) |
|
Device |
3020 |
1301 |
0x515 |
FLASH_HW_VERSION |
Read-only |
|
|
HW version |
|
AV56 |
Present Value |
1500 |
0x5DC |
SETPOINT_VALUE |
Read/write |
|
0-500 |
Temperature setpoint value |
|
AI 3 |
Present Value |
1501 |
0x5DD |
EFFECTIVE_SETPOINT |
Read-only |
|
|
Sum of setpoint and offset values |
|
AV 57 |
Present Value |
1502 |
0x5DE |
DEFAULT_SETPOINT |
Read/write |
210 |
0-500 |
Default temperature setpoint |
|
AV 58 |
Present Value |
1503 |
0x5DF |
OFFSET_SETPOINT |
Read/write |
0 |
0-500 |
Temperature offset for setpoint |
|
AV 56 |
Low Limit |
1504 |
0x5E0 |
SETPOINT_LOW_LIMIT |
Read/write |
180 |
|
Min. available setpoint value |
|
AV 56 |
High Limit |
1505 |
0x5E1 |
SETPOINT_HIGH_LIMIT |
Read/write |
240 |
|
Max. available setpoint value |
|
AV 59 |
Present Value |
1506 |
0x5E2 |
OFFSET_RANGE |
Read/write |
30 |
0-500 |
Limits offset value |
|
AV 56 |
4206 |
1507 |
0x5E3 |
SETPOINT_STEP |
Read/write |
10 |
|
Setpoint step value |
|
|
|
1512 |
0x5E8 |
SETPOINT_CONFIGURATION |
Read/write |
|
|
Setpoint configuration of parameters: Visible, Editable, Operating mode, Setpoint display, ThirdPointActive |
|
AV56 |
Out Of Service |
|
|
VISIBLE |
|
|
|
Enables or disables the temperature setpoint to be visible on the panel's display |
|
AV56 |
4200 |
|
|
EDITABLE |
|
|
|
Enables or disables editing of the temperature setpoint locally from the panel |
|
BO55 |
Present Value |
|
|
OPERATING_MODE |
|
|
|
Sets the operating mode of the temperature setpoint configuration |
|
BO56 |
Present Value |
|
|
SETPOINT_DISPLAY |
|
|
|
Configures the temperature setpoint display |
|
AV56 |
4202 |
|
|
THIRD_POINT_ACTIVE |
|
|
|
Enables or disables decimal values in the temperature setpoint |
|
MSV0 |
Present Value |
1600 |
0x640 |
FAN_CURRENT_SPEED |
Read/write |
0 |
|
Fan speed |
|
MSV1 |
Present Value |
1601 |
0x641 |
FAN_MODE |
Read/write |
1 |
|
Fan mode |
|
MSV2 |
Present Value |
1602 |
0x642 |
FAN_TYPE |
Read/write |
|
|
Fan type |
|
41614 |
|
1613 |
0x64D |
FAN_CONFIGURATION |
Read/write |
2 |
|
|
|
MSV1 |
Editable |
|
|
EDITABLE |
|
|
|
Activates or inactivated editing fan modes locally in the panel |
|
BO58 |
Present Value |
|
|
FAN_PART_EDITABLE |
|
|
|
Configures editing of fan modes |
|
BO60 |
Present Value |
|
|
FAN_CONFIG_LOCAL_MODE |
|
|
|
Local/BMS mode |
|
MSV3 |
Present Value |
1700 |
0x6A4 |
OCCUPANCY_CURRENT_STATUS |
Read/write |
|
|
Occupancy status |
|
MSV4 |
Present Value |
1701 |
0x6A5 |
OCCUPANCY_MODE |
Read/write |
|
|
Occupancy mode |
|
|
|
1706 |
0x6AA |
OCCUPANCY_CONFIGURATION |
Read/write |
2 |
|
|
|
MSV4 |
4200 |
|
|
EDITABLE |
|
|
|
Activates or inactivated editing occupancy statutes locally in the panel |
|
BO62 |
Present Value |
|
|
OCCUPANCY_CONFIG_LOCAL_MODE |
|
|
|
Local/BMS mode |
List of BACnet objects