Default Settings

Out of the box device as well as after restoring default values procedure, has got the following default settings:

Name

Default Value

User baud rate

76800

Stop bits

1

Data bits

8

Parity bits

0

Response delay

0

I1-I4 digital input counters

0

Non-volatile values stored in the EEPROM memory

Cleared

I/O configuration

Cleared

Default values

Restoring Default Settings

To restore the default iSMA-B-FCU device settings, follow the steps below:

Step 1: Turn the power supply off.

Step 2: Set the 6th switch of the Protocol DIP switch to ON.

Step 3: Turn on the power supply, wait until the power LED blinks.