Breadcrumbs

LpCO2Sensor


This page is a source for LpCO2Sensor (AAC).


Note: Component applicable for the LP and Touch Point panels.

The LpCO2Sensor component is responsible for reading values and configuration of the CO2 sensor.

85 LpCO2Sensor_2.png

The LpCO2Sensor component

The LpCO2Sensor component has the following slots:

  • Status: shows the component’s status;

  • Fault Cause: shows the fault cause description;

  • Fault Status: informs about the point error status (true: point read/write error);

  • Enable: enables or disables the component (true: enabled, false: disabled);

  • Poll Frequency: allows to set the reading poll frequency (fast, normal, slow);

  • Out: the CO2 sensor value;

  • Display Name: allows to set the CO2 sensor name on the display (up to 4 characters, only ASCII characters, only for the LP panel);

  • Visibility: activates or inactivates the sensor value on the display;

  • Sensor Offset: sets the CO2 sensor offset value;

  • Sensor Filter: sets the CO2 sensor reading filter time in seconds;

  • Config Trigger: sends configuration parameters to the device components on rising edge (Display Name, Visibility, Sensor Offset, Sensor Filter).

The LpCO2Sensor component has the following right-click menu actions:

  • Read: reads the remote device CO2 sensor value and updates the Out slot;

  • Read Config: reads configuration parameters from the panel (Display Name, Visibility, Sensor Offset, Sensor Filter);

  • Write Config: writes configuration parameters to the panel (Display Name, Visibility, Sensor Offset, Sensor Filter).