Breadcrumbs

FanSpeed


This page is a source page for FanSpeed (AAC).


Note: Component applicable for the LP, Touch Point, and FP panels.

The FanSpeed component is responsible for configuring fan settings in the panel.

83 FanSpeed_2.png

The FanSpeed component

The FanSpeed component has the following slots:

  • Status: shows the component’s status;

  • Fault Cause: shows the fault cause description;

  • Fault Status: informs about the point error status (true: point read/write error);

  • Enable: enables or disables the component (true: enabled, false: disabled);

  • Poll Frequency: allows to set the reading poll frequency (fast, normal, slow);

  • Write Type: defines a method of writing values (COV, COV_PollFrequency, PollFrequency, COV_LinkSet);

  • Trigger: allows to force sending values on rising edge;

  • Fan Current Speed: sets the current speed of fan (Off, ManualSpeed1, ManualSpeed2, ManualSpeed3, AutoSpeed1, AutoSpeed2, AutoSpeed3)

  • Fan Current Mode: sets the current mode of fan (Off, ManualSpeed1, ManualSpeed2, ManualSpeed3, Auto).

  • Visibility: allows to activate or deactivate the point on the display (only for the LP panel);

  • Editable: enables or disables editing of a fan speed in the panel;

  • Part Editable: allows to set an editing mode in the panel (FullyEditable, AutoOffMode);

  • Fast Edit Mode: enables a fast edit mode in the panel (only for the LP panel);

  • Mode: identifies a way of controlling the panel (LocalMode, BmsMode);

  • Fan Icon Flashing Time: allows to set a flashing time of icons on the display (only for the LP panel);

  • Fan Type: sets a type of fan (0-10 V, 1-speed, 2-speed, 3-speed);

  • Fan Mode0 Name-Fan Mode4 Name: allows to set different fan mode names (up to 4, only ASCII characters; only for the LP panel);

  • Config Trigger: on rising edge sends configuration parameters to the device components (Editable, Part Editable, Mode, Fan Type).

The FanSpeed component has the following actions:

  • Read: reads the panel’s fan values and updates the Fan Current Speed and Fan Current Mode slots;

  • Read Config: reads configuration parameters from the panel (Editable, Part Editable, Mode, Fan Type);

  • Write Config: writes configuration parameters to the panel (Editable, Part Editable, Mode, Fan Type).