No. | 1 |
---|---|
Sensor | 10K3A1 |
β coefficient | 3975K |
Manufacturers | Cylon, Honeywell, Johnson, Satchwell, Seachange |
°C | Ω |
-45 | 491749 |
-40 | 335671 |
-35 | 241840 |
-30 | 176683 |
-25 | 131251 |
-20 | 96974 |
-15 | 72895 |
-10 | 55298 |
-5 | 42314 |
0 | 32650 |
5 | 25396 |
10 | 19904 |
15 | 15714 |
20 | 12494 |
25 | 10000 |
30 | 8056 |
35 | 6530 |
40 | 5325 |
45 | 4367 |
50 | 3601 |
55 | 2985 |
60 | 2487 |
65 | 2082 |
70 | 1751 |
75 | 1480 |
80 | 1256 |
85 | 1070 |
90 | 916 |
95 | 787 |
100 | 678 |
105 | 587 |
110 | 510 |
115 | 444 |
120 | 388 |
125 | 340 |
No. | 2 |
---|---|
Sensor | 10K4A1 |
β coefficient | 3695K |
Manufacturers | Andover, Delta Controls, Siebe, York |
°C | Ω |
-45 | 330749 |
-40 | 239831 |
-35 | 181532 |
-30 | 135233 |
-25 | 105081 |
-20 | 78930 |
-15 | 61030 |
-10 | 47549 |
-5 | 37316 |
0 | 29490 |
5 | 23462 |
10 | 18787 |
15 | 15136 |
20 | 12268 |
25 | 10000 |
30 | 8197 |
35 | 6754 |
40 | 5594 |
45 | 4656 |
50 | 3893 |
55 | 3271 |
60 | 2760 |
65 | 2339 |
70 | 1990 |
75 | 1700 |
80 | 1458 |
85 | 1255 |
90 | 1084 |
95 | 939 |
100 | 817 |
105 | 713 |
110 | 624 |
115 | 547 |
120 | 482 |
125 | 426 |
No. | 3 |
---|---|
Sensor | 10K |
β coefficient | 3435K |
Manufacturers | Carel |
°C | Ω |
-40 | 188500 |
-35 | 144100 |
-30 | 111300 |
-25 | 86430 |
-20 | 67770 |
-15 | 53410 |
-10 | 42470 |
-5 | 33900 |
0 | 27280 |
5 | 22050 |
10 | 17960 |
15 | 14690 |
20 | 12090 |
25 | 10000 |
30 | 8313 |
35 | 6940 |
40 | 5827 |
45 | 4912 |
50 | 4161 |
55 | 3536 |
60 | 3020 |
65 | 2588 |
70 | 2228 |
75 | 1924 |
80 | 1668 |
85 | 1451 |
90 | 1266 |
95 | 1108 |
100 | 973 |
105 | 857 |
110 | 758 |
115 | 672 |
120 | 597 |
125 | 531 |
No. | 4 |
---|---|
Sensor | 20K6A1 |
β coefficient | 4262K |
Manufacturers | Honeywell |
°C | Ω |
-40 | 806800 |
-35 | 574400 |
-30 | 413400 |
-25 | 300400 |
-20 | 220600 |
-15 | 163480 |
-10 | 122260 |
-5 | 92220 |
0 | 70140 |
5 | 53780 |
10 | 41540 |
15 | 32340 |
20 | 25340 |
25 | 20000 |
30 | 15886 |
35 | 12698 |
40 | 10212 |
45 | 8260 |
50 | 6718 |
55 | 5494 |
60 | 4518 |
65 | 3732 |
70 | 3098 |
75 | 2586 |
80 | 2166 |
85 | 1823 |
90 | 1541 |
95 | 1308 |
100 | 1114 |
105 | 953 |
110 | 818 |
115 | 704 |
120 | 609 |
125 | 528 |
No. | 5 |
---|---|
Sensor | 2.2K3A1 |
β coefficient | 3975K |
Manufacturers | Ambiflex, Johnson |
°C | Ω |
-50 | 154464 |
-45 | - |
-40 | 77081 |
-35 | - |
-30 | 40330 |
-25 | - |
-20 | 22032 |
-15 | - |
-10 | 12519 |
-5 | 9529 |
0 | 7373 |
5 | 5719 |
10 | 4487 |
15 | 3539 |
20 | 2814 |
25 | 2252 |
30 | 1814 |
35 | 1471 |
40 | 1199 |
45 | 983 |
50 | 812 |
55 | 672 |
60 | 561 |
65 | 469 |
70 | 395 |
75 | 333 |
80 | 284 |
85 | 241 |
90 | 207 |
95 | 177 |
100 | 154 |
105 | 132 |
110 | 116 |
115 | - |
120 | 88 |
125 | - |
No. | 6 |
---|---|
Sensor | 3K3A1 |
β coefficient | 3975K |
Manufacturers | Alerton |
°C | Ω |
-50 | 200348 |
-45 | 150524 |
-40 | 100701 |
-35 | 76853 |
-30 | 53005 |
-25 | 41048 |
-20 | 29092 |
-15 | 21868 |
-10 | 16589 |
-5 | 12694 |
0 | 9795 |
5 | 7619 |
10 | 5971 |
15 | 4714 |
20 | 3748 |
25 | 3000 |
30 | 2417 |
35 | 1959 |
40 | 1598 |
45 | 1310 |
50 | 1080 |
55 | 896 |
60 | 746 |
65 | 625 |
70 | 526 |
75 | 444 |
80 | 377 |
85 | 321 |
90 | 275 |
95 | 236 |
100 | 204 |
105 | 176 |
110 | 153 |
115 | 133 |
120 | 117 |
125 | 102 |
No. | 7 |
---|---|
Sensor | 30K6A1 |
β coefficient | 4262K |
Manufacturers | Drayton |
°C | Ω |
-30 | 622911 |
-25 | 477393 |
-20 | 331876 |
-15 | 245785 |
-10 | 183697 |
-5 | 138502 |
0 | 105305 |
5 | 60713 |
10 | 62347 |
15 | 48511 |
20 | 38019 |
25 | 30000 |
30 | 23828 |
35 | 19046 |
40 | 15317 |
45 | 12390 |
50 | 10079 |
55 | 8243 |
60 | 6777 |
65 | 5600 |
70 | 4650 |
75 | 3879 |
80 | 3251 |
85 | 2737 |
90 | 2313 |
95 | 1963 |
100 | 1672 |
105 | 1430 |
110 | 1228 |
115 | 1058 |
120 | 915 |
125 | 793 |
No. | 8 |
---|---|
Sensor | TAC1 |
β coefficient | 3500K |
Manufacturers | TAC |
°C | Ω |
-40 | 39024 |
-35 | 29358 |
-30 | 22284 |
-25 | 17073 |
-20 | 13192 |
-15 | 10276 |
-10 | 8068 |
-5 | 6382 |
0 | 5085 |
5 | 4078 |
10 | 3294 |
15 | 2676 |
20 | 2188 |
25 | 1800 |
30 | 1488 |
35 | 1237 |
40 | 1034 |
45 | 869 |
50 | 733 |
55 | 622 |
60 | 529 |
65 | 453 |
70 | 389 |
75 | 335 |
80 | 290 |
85 | 252 |
90 | 220 |
95 | 192 |
100 | 169 |
105 | 149 |
110 | 131 |
115 | 116 |
120 | 103 |
125 | 92 |
No. | 9 |
---|---|
Sensor | SIE1 |
Manufacturers | Barber Colman, Siebe |
°C | Ω |
-50 | 10732 |
-45 | 10624 |
-40 | 10517 |
-35 | 10344 |
-30 | 10172 |
-25 | 9913 |
-20 | 9654 |
-15 | 9320 |
-10 | 8933 |
-5 | 8496 |
0 | 8044 |
5 | 7489 |
10 | 6938 |
15 | 6370 |
20 | 5798 |
25 | 5238 |
30 | 4696 |
35 | 4185 |
40 | 3707 |
45 | 3271 |
50 | 2875 |
55 | 2521 |
60 | 2206 |
65 | 1929 |
70 | 1685 |
75 | 1472 |
80 | 1287 |
85 | 1127 |
90 | 986 |
95 | 866 |
100 | 760 |
105 | 670 |
110 | 590 |
115 | 522 |
120 | 462 |
125 | 410 |
No. | 10 |
---|---|
Sensor | SAT1 |
Manufacturers | Satchwell |
°C | Ω |
-45 | 9652 |
-40 | 9584 |
-35 | 9467 |
-30 | 9349 |
-25 | 9159 |
-20 | 8968 |
-15 | 8708 |
-10 | 8396 |
-5 | 8031 |
0 | 7614 |
5 | 7150 |
10 | 6649 |
15 | 6121 |
20 | 5580 |
25 | 5039 |
30 | 4513 |
35 | 4012 |
40 | 3545 |
45 | 3117 |
50 | 2730 |
55 | 2386 |
60 | 2082 |
65 | 1816 |
70 | 1585 |
75 | 1385 |
80 | 1213 |
85 | 1064 |
90 | 937 |
95 | 828 |
100 | 734 |
105 | 654 |
110 | 585 |
115 | 525 |
120 | 474 |
125 | 429 |
No. | 11 |
---|---|
Sensor | PT1000 |
Manufacturers | Honeywell, Sauter, Serck, Siebe, Cylon |
°C | Ω |
-50 | 803,1 |
-40 | 842,7 |
-30 | 882,2 |
-20 | 921,6 |
-10 | 960,9 |
0 | 1000,0 |
10 | 1039,0 |
20 | 1077,9 |
30 | 1116,7 |
40 | 1155,4 |
50 | 1194,0 |
60 | 1232,4 |
70 | 1270,8 |
80 | 1309,0 |
90 | 1347,1 |
100 | 1385,1 |
110 | 1422,9 |
120 | 1460,7 |
130 | 1498,3 |
140 | 1535,8 |
150 | 1573,3 |
160 | 1610,5 |
170 | 1647,7 |
180 | 1684,8 |
190 | 1721,7 |
200 | 1758,6 |
210 | 1795,3 |
220 | 1831,9 |
230 | 1868,4 |
240 | 1904,7 |
250 | 1941,0 |
260 | 1977,1 |
270 | 2013,1 |
280 | 2049,0 |
290 | 2084,8 |
300 | 2120,5 |
310 | 2156,1 |
320 | 2191,5 |
330 | 2226,8 |
340 | 2262,1 |
350 | 2297,2 |
360 | 2332,1 |
370 | 2367,0 |
380 | 2401,8 |
390 | 2436,4 |
400 | 2470,9 |
No. | 12 |
---|---|
Sensor | NI1000 |
Manufacturers | Sauter |
°C | Ω |
-50 | 742,6 |
-40 | 791,3 |
-30 | 841,5 |
-20 | 893,0 |
-10 | 945,8 |
0 | 1000,0 |
10 | 1055,5 |
20 | 1112,4 |
30 | 1170,6 |
40 | 1230,1 |
50 | 1291,1 |
60 | 1353,4 |
70 | 1417,2 |
80 | 1482,5 |
90 | 1549,4 |
100 | 1617,8 |
110 | 1687,9 |
120 | 1759,8 |
130 | 1833,4 |
140 | 1909,0 |
150 | 1986,6 |
No. | 13 |
---|---|
Sensor | NI1000 21C (ºC) |
Manufacturers | Distech |
°C | Ω |
-40 | 699,3 |
-30 | 745,5 |
-20 | 792,8 |
-10 | 841,2 |
0 | 891,0 |
10 | 942,0 |
20 | 994,3 |
30 | 1047,8 |
40 | 1102,6 |
50 | 1158,5 |
60 | 1215,8 |
70 | 1274,3 |
80 | 1334,4 |
90 | 1407,8 |
100 | 1473,1 |
110 | 1524,0 |
No. | 14 |
---|---|
Sensor | NI1000 LG (ºC) |
Manufacturers | LG |
°C | Ω |
-50 | 790,9 |
-40 | 830,8 |
-30 | 871,7 |
-20 | 913,5 |
-10 | 956,2 |
0 | 1000,0 |
10 | 1044,8 |
20 | 1090,7 |
30 | 1137,6 |
40 | 1185,7 |
50 | 1235,0 |
60 | 1285,4 |
70 | 1337,1 |
80 | 1390,1 |
90 | 1444,4 |
100 | 1500,0 |
110 | 1557,0 |
120 | 1615,4 |
130 | 1675,2 |
140 | 1736,5 |
150 | 1799,3 |