Skip to main content
Skip table of contents

List of Supported Temperature Sensors

No.

1

Sensor

10K3A1

β coefficient

3975K

Manufacturers

Cylon, Honeywell, Johnson, Satchwell, Seachange

°C

Ω

-45

491749

-40

335671

-35

241840

-30

176683

-25

131251

-20

96974

-15

72895

-10

55298

-5

42314

0

32650

5

25396

10

19904

15

15714

20

12494

25

10000

30

8056

35

6530

40

5325

45

4367

50

3601

55

2985

60

2487

65

2082

70

1751

75

1480

80

1256

85

1070

90

916

95

787

100

678

105

587

110

510

115

444

120

388

125

340

No.

2

Sensor

10K4A1

β coefficient

3695K

Manufacturers

Andover, Delta Controls, Siebe, York

°C

Ω

-45

330749

-40

239831

-35

181532

-30

135233

-25

105081

-20

78930

-15

61030

-10

47549

-5

37316

0

29490

5

23462

10

18787

15

15136

20

12268

25

10000

30

8197

35

6754

40

5594

45

4656

50

3893

55

3271

60

2760

65

2339

70

1990

75

1700

80

1458

85

1255

90

1084

95

939

100

817

105

713

110

624

115

547

120

482

125

426

No.

3

Sensor

10K

β coefficient

3435K

Manufacturers

Carel

°C

Ω

-40

188500

-35

144100

-30

111300

-25

86430

-20

67770

-15

53410

-10

42470

-5

33900

0

27280

5

22050

10

17960

15

14690

20

12090

25

10000

30

8313

35

6940

40

5827

45

4912

50

4161

55

3536

60

3020

65

2588

70

2228

75

1924

80

1668

85

1451

90

1266

95

1108

100

973

105

857

110

758

115

672

120

597

125

531

No.

4

Sensor

20K6A1

β coefficient

4262K

Manufacturers

Honeywell

°C

Ω

-40

806800

-35

574400

-30

413400

-25

300400

-20

220600

-15

163480

-10

122260

-5

92220

0

70140

5

53780

10

41540

15

32340

20

25340

25

20000

30

15886

35

12698

40

10212

45

8260

50

6718

55

5494

60

4518

65

3732

70

3098

75

2586

80

2166

85

1823

90

1541

95

1308

100

1114

105

953

110

818

115

704

120

609

125

528

No.

5

Sensor

2.2K3A1

β coefficient

3975K

Manufacturers

Ambiflex, Johnson

°C

Ω

-50

154464

-45

-

-40

77081

-35

-

-30

40330

-25

-

-20

22032

-15

-

-10

12519

-5

9529

0

7373

5

5719

10

4487

15

3539

20

2814

25

2252

30

1814

35

1471

40

1199

45

983

50

812

55

672

60

561

65

469

70

395

75

333

80

284

85

241

90

207

95

177

100

154

105

132

110

116

115

-

120

88

125

-

No.

6

Sensor

3K3A1

β coefficient

3975K

Manufacturers

Alerton

°C

Ω

-50

200348

-45

150524

-40

100701

-35

76853

-30

53005

-25

41048

-20

29092

-15

21868

-10

16589

-5

12694

0

9795

5

7619

10

5971

15

4714

20

3748

25

3000

30

2417

35

1959

40

1598

45

1310

50

1080

55

896

60

746

65

625

70

526

75

444

80

377

85

321

90

275

95

236

100

204

105

176

110

153

115

133

120

117

125

102

No.

7

Sensor

30K6A1

β coefficient

4262K

Manufacturers

Drayton

°C

Ω

-30

622911

-25

477393

-20

331876

-15

245785

-10

183697

-5

138502

0

105305

5

60713

10

62347

15

48511

20

38019

25

30000

30

23828

35

19046

40

15317

45

12390

50

10079

55

8243

60

6777

65

5600

70

4650

75

3879

80

3251

85

2737

90

2313

95

1963

100

1672

105

1430

110

1228

115

1058

120

915

125

793

No.

8

Sensor

TAC1

β coefficient

3500K

Manufacturers

TAC

°C

Ω

-40

39024

-35

29358

-30

22284

-25

17073

-20

13192

-15

10276

-10

8068

-5

6382

0

5085

5

4078

10

3294

15

2676

20

2188

25

1800

30

1488

35

1237

40

1034

45

869

50

733

55

622

60

529

65

453

70

389

75

335

80

290

85

252

90

220

95

192

100

169

105

149

110

131

115

116

120

103

125

92

No.

9

Sensor

SIE1

Manufacturers

Barber Colman, Siebe

°C

Ω

-50

10732

-45

10624

-40

10517

-35

10344

-30

10172

-25

9913

-20

9654

-15

9320

-10

8933

-5

8496

0

8044

5

7489

10

6938

15

6370

20

5798

25

5238

30

4696

35

4185

40

3707

45

3271

50

2875

55

2521

60

2206

65

1929

70

1685

75

1472

80

1287

85

1127

90

986

95

866

100

760

105

670

110

590

115

522

120

462

125

410

No.

10

Sensor

SAT1

Manufacturers

Satchwell

°C

Ω

-45

9652

-40

9584

-35

9467

-30

9349

-25

9159

-20

8968

-15

8708

-10

8396

-5

8031

0

7614

5

7150

10

6649

15

6121

20

5580

25

5039

30

4513

35

4012

40

3545

45

3117

50

2730

55

2386

60

2082

65

1816

70

1585

75

1385

80

1213

85

1064

90

937

95

828

100

734

105

654

110

585

115

525

120

474

125

429

No.

11

Sensor

PT1000

Manufacturers

Honeywell, Sauter, Serck, Siebe, Cylon

°C

Ω

-50

803,1

-40

842,7

-30

882,2

-20

921,6

-10

960,9

0

1000,0

10

1039,0

20

1077,9

30

1116,7

40

1155,4

50

1194,0

60

1232,4

70

1270,8

80

1309,0

90

1347,1

100

1385,1

110

1422,9

120

1460,7

130

1498,3

140

1535,8

150

1573,3

160

1610,5

170

1647,7

180

1684,8

190

1721,7

200

1758,6

210

1795,3

220

1831,9

230

1868,4

240

1904,7

250

1941,0

260

1977,1

270

2013,1

280

2049,0

290

2084,8

300

2120,5

310

2156,1

320

2191,5

330

2226,8

340

2262,1

350

2297,2

360

2332,1

370

2367,0

380

2401,8

390

2436,4

400

2470,9

No.

12

Sensor

NI1000

Manufacturers

Sauter

°C

Ω

-50

742,6

-40

791,3

-30

841,5

-20

893,0

-10

945,8

0

1000,0

10

1055,5

20

1112,4

30

1170,6

40

1230,1

50

1291,1

60

1353,4

70

1417,2

80

1482,5

90

1549,4

100

1617,8

110

1687,9

120

1759,8

130

1833,4

140

1909,0

150

1986,6

No.

13

Sensor

NI1000 21C (ºC)

Manufacturers

Distech

°C

Ω

-40

699,3

-30

745,5

-20

792,8

-10

841,2

0

891,0

10

942,0

20

994,3

30

1047,8

40

1102,6

50

1158,5

60

1215,8

70

1274,3

80

1334,4

90

1407,8

100

1473,1

110

1524,0

No.

14

Sensor

NI1000 LG (ºC)

Manufacturers

LG

°C

Ω

-50

790,9

-40

830,8

-30

871,7

-20

913,5

-10

956,2

0

1000,0

10

1044,8

20

1090,7

30

1137,6

40

1185,7

50

1235,0

60

1285,4

70

1337,1

80

1390,1

90

1444,4

100

1500,0

110

1557,0

120

1615,4

130

1675,2

140

1736,5

150

1799,3