Other Parameters
Other parameters of the TP panel can be retrieved from the following registers and objects, or in the iSMA Configurator:
LIVE_TIME: shows uptime of the device since the last reset;
- Modbus register: 30012;
- BACnet object: AI0, property: Present Value;
VERSION_TYPE: allows to read version and type of the panel and enable 1 of 4 available actions. The first byte of the register indicates a version of the device, and the second one–type of the device;
- Modbus register: 40001;
- BACnet object: DEVICE, property: 3030;
Value | Bits 0-7 | Bits 8-15 | |
---|---|---|---|
Type | Panel's version | 11210(0x7016) | |
Panel in bootloader | 23910(0xEF16) | ||
Version | Firmware version multiplied by 10 | 1010(0x0A16) means 1.0 firmware version |
The VERSION_TYPE register also allows to enable 1 of 4 available actions: reset panel, reload settings, reset settings, enter bootloader. If the register receives one of the following values, it invokes a relevant action and resumes its regular values afterwards (type and version):
Decimal Value | Hex Value | Action |
---|---|---|
511 | 0x01FF | Reset panel |
767 | 0x02FF | Reload settings |
1023 | 0x03FF | Reset settings |
1279 | 0x04FF | Enter bootloader |
FLASH_DEVICE_TYPE: indicates the panel's version and type;
- Modbus register: 31301;
- BACnet object: N/A;
Bit | Name | Description |
---|---|---|
0-7 | VERSION_TYPE | Copy of the 40001 register's value |
8-15 | DEVICE_TYPE | 0: TP, 1: not available |
31 | LCD_PRESENT | 0: with display, 1: without display |
FLASH_HW_VERSION: indicates the panel's hardware version;
- Modbus register 31303;
- BACnet object: DEVICE, property: 3020;
FLASH_BOOT_VERSION: indicates the panel's bootloader version;
- Modbus register: 31304;
- BACnet object: N/A;
FW_VERSION: indicates the panel's firmware version separated from the VERSION_TYPE register's value;
- Modbus register: 31305;
- BACnet object: N/A;
FLASH_SERIAL_NUMBER: indicates the panel's serial number;
- Modbus registers 31306-31309;
- BACnet object: N/A.