Module Registers
Registered Access
Modbus Address | Decimal Address | Hex Address | Register Name | Access | Description |
---|---|---|---|---|---|
30001 | 0 | 0x00 | Version/Type | Read | Version and type of the device |
30002 | 1 | 0x01 | Switches | Read | Switches state |
40003 | 2 | 0x02 | Baud Rate | Read/write | RS485 baud rate |
40004 | 3 | 0x03 | Stop Bits & Data Bits | Read/write | No. of stop bits & data bits |
40005 | 4 | 0x04 | Parity | Read/write | Parity bit |
40006 | 5 | 0x05 | Response Delay | Read/write | Response delay in ms |
40007 | 6 | 0x06 | Modbus Mode | Read/write | Modbus mode (ASCII or RTU) |
40010 | 9 | 0x09 | Analog Filtering | Read/write | Configuration analog filtering |
40033 | 32 | 0x20 | Received Packets LSR (Least Significant Register) | Read/write | No. of received packets |
40034 | 33 | 0x21 | Received Packets MSR (Most Significant Register) | Read/write | |
40035 | 34 | 0x22 | Incorrect Packets LSR | Read/write | No. of received packets with error |
40036 | 35 | 0x23 | Incorrect Packets MSR | Read/write | |
40037 | 36 | 0x24 | Sent Packets LSR | Read/write | No. of sent packets |
40038 | 37 | 0x25 | Sent Packets MSR | Read/write | |
30051 | 50 | 0x32 | Inputs | Read | Connected sensors |
40052 | 51 | 0x33 | Outputs | Read/write | Alarms state |
30053 | 52 | 0x34 | Temperature 1 | Read | Temperature or measured analog |
30054 | 53 | 0x35 | Temperature 2 | Read | |
30055 | 54 | 0x36 | Temperature 3 | Read | |
30056 | 55 | 0x37 | Temperature 4 | Read | |
30057 | 56 | 0x38 | Temperature 5 | Read | |
30058 | 57 | 0x39 | Temperature 6 | Read | |
30059 | 58 | 0x3A | Alarm Temperature 1 | Read | Alarm temperature for alarm output 1 |
30060 | 59 | 0x3B | Alarm Temperature 2 | Read | Alarm temperature for alarm output 2 |
30061 | 60 | 0x3C | Junction Temperature | Read | Module junction temperature |
30062 | 61 | 0x3D | Measurement Current | Read | Measurement current |
40063 | 62 | 0x3E | MAX Alarm Level 1 | Read/write | If the temperature exceeds this value the corresponding alarm flag is set |
40064 | 63 | 0x3F | MAX Alarm Level 2 | Read/write | |
40065 | 64 | 0x40 | MAX Alarm Level 3 | Read/write | |
40066 | 65 | 0x41 | MAX Alarm Level 4 | Read/write | |
40067 | 66 | 0x42 | MAX Alarm Level 5 | Read/write | |
40068 | 67 | 0x43 | MAX Alarm Level 6 | Read/write | |
40069 | 68 | 0x44 | MIN Alarm Level 1 | Read/write | If the temperature is below this value corresponding alarm flag is set |
40070 | 69 | 0x45 | MIN Alarm Level 2 | Read/write | |
40071 | 70 | 0x46 | MIN Alarm Level 3 | Read/write | |
40072 | 71 | 0x47 | MIN Alarm Level 4 | Read/write | |
40073 | 72 | 0x48 | MIN Alarm Level 5 | Read/write | |
40074 | 73 | 0x49 | MIN Alarm Level 6 | Read/write | |
40075 | 74 | 0x4A | Alarm Settings 1 | Read/write | Alarm Settings |
40076 | 75 | 0x4B | Alarm Settings 2 | Read/write | |
40077 | 76 | 0x4C | Alarm Settings 3 | Read/write | |
40078 | 77 | 0x4D | Alarm Settings 4 | Read/write | |
40079 | 78 | 0x4E | Alarm Settings 5 | Read/write | |
40080 | 79 | 0x4F | Alarm Settings 6 | Read/write | |
40081 | 80 | 0x50 | Constant Junction Temperature | Read/write | Value of junction temperature |
40082 | 81 | 0x51 | Junction Temperature Offset | Read/write | Junction temperature offset |
40083 | 82 | 0x52 | Input 1 Settings | Read/write | Analog input mode: |
40084 | 83 | 0x53 | Input 2 Settings | Read/write | |
40085 | 84 | 0x54 | Input 3 Settings | Read/write | |
40086 | 85 | 0x55 | Input 4 Settings | Read/write | |
40087 | 86 | 0x56 | Input 5 Settings | Read/write | |
40088 | 87 | 0x57 | Input 6 Settings | Read/write | |
40089 | 88 | 0x58 | Output 1 Settings | Read/write | Alarm output settings |
40090 | 89 | 0x59 | Output 2 Settings | Read/write | |
40091 | 90 | 0x5A | Alarm Value 1 | Read/write | Alarm value for outputs |
40092 | 91 | 0x5B | Alarm Value 2 | Read/write | |
40093 | 92 | 0x5C | Alarm Hysteresis 1 | Read/write | The hysteresis value for alarm outputs |
40094 | 93 | 0x5D | Alarm Hysteresis 2 | Read/write | |
40095 | 94 | 0x5E | Input Resistance 1 | Read/write | Lead wire resistance for each input |
40096 | 95 | 0x5F | Input Resistance 2 | Read/write | |
40097 | 96 | 0x60 | Input Resistance 3 | Read/write | |
40098 | 97 | 0x61 | Input Resistance 4 | Read/write | |
40099 | 98 | 0x62 | Input Resistance 5 | Read/write | |
40100 | 99 | 0x63 | Input Resistance 6 | Read/write |
Bit Access
Modbus Address | Decimal Address | Hex | Register Name | Access | Description |
---|---|---|---|---|---|
801 | 800 | 0x320 | Input 1 | Read | Set when the sensor is connected |
802 | 801 | 0x321 | Input 2 | Read | Set when the sensor is connected |
803 | 802 | 0x322 | Input 3 | Read | Set when the sensor is connected |
804 | 803 | 0x323 | Input 4 | Read | Set when the sensor is connected |
805 | 804 | 0x324 | Input 5 | Read | Set when the sensor is connected |
806 | 805 | 0x325 | Input 6 | Read | Set when the sensor is connected |
817 | 816 | 0x330 | Alarm 1 | Read | Alarm state 1 |
818 | 817 | 0x331 | Alarm 2 | Read | Alarm state 2 |
819 | 818 | 0x332 | Alarm 3 | Read | Alarm state 3 |
820 | 819 | 0x333 | Alarm 4 | Read | Alarm state 4 |
821 | 820 | 0x334 | Alarm 5 | Read | Alarm state 5 |
822 | 821 | 0x335 | Alarm 6 | Read | Alarm state 6 |
823 | 822 | 0x336 | Digital Output 1 | Read/write | State of digital output 1 |
824 | 823 | 0x337 | Digital Output 2 | Read/write | State of digital output 2 |