M-Bus Configuration Registers

WARNING!

Changing the parameters configuring a transmission (except for registers which value is read from the switch) will only take effect after restarting the device.

Counter of Received Messages (30015)

The 16-bit register with the number of valid M-Bus messages received by the device from last powering up. The value is reset after a power cycle or after changing transmission parameters.

Counter of Sent Messages (30017)

The 16-bit register with the number of M-Bus messages sent by the device from last powering up. The value is reset after a power cycle or after changing transmission parameters.

Counter of Alarms (30019)

The 16-bit register with the number of M-Bus alarms from last powering up. An alarm is detected if current bus exceeds acceptable level (130 mA). The value is reset after a power cycle or after changing transmission parameters.