Modbus Address

Decimal Address

Hex Address

Register Name

Access

Description

40051

50

0x32

MAIN_MENU_NUMERIC1

PRESENTVALUE

Read/write
Memory

Present value of the parameter.

40320

319

0x13F

MAIN_MENU_NUMERIC1

NAME (32–bits)

Read/write
Memory

User-defined parameter name displayed.


40322

321

0x141

MAIN_MENU_NUMERIC1

PRIORITY

Read/write
Memory

Priority of the parameter for sequence of displaying  in the main menu.

40323

322

0x142

MAIN_MENU_NUMERIC1

CONFIGURATION

Read/write
Memory

Bit

Name

0

1

0

Active

Not active(def)

Active(def)

2

FirstPointActive

Not decimal(def)

Decimal(def)

3

SecondPointActive

Not decimal(def)

Decimal(def)

4

ThirdPointActive

Not decimal(def)

Decimal(def)

6

C unit active

not_visible(def)

visible

7

F unit active

not_visible(def)

visible

8

Pa unit active

not_visible(def)

visible

9

Lx unit active

not_visible(def)

visible

10

ppm unit active

not_visible(def)

visible

11

m3/h unit active

not_visible(def)

visible

12

%Rh unit active

not_visible(def)

visible

13

l/s unit active

not_visible(def)

visible

14

% unit active

not_visible(def)

visible

15

h unit active

not_visible(def)

visible

40052

51

0x33

MAIN_MENU_NUMERIC2

PRESENTVALUE

Read/write
Memory

Present value of the parameter.

40325

324

0x144

MAIN_MENU_NUMERIC2

NAME (32–bits)

Read/write
Memory

Displaying user-defined parameter name.

40327

326

0x146

MAIN_MENU_NUMERIC2

PRIORITY

Read/write
Memory

Priority of the parameter for sequence of display in the main menu

40328

327

0x147

MAIN_MENU_NUMERIC2

CONFIGURATION

Read/write
Memory

See the table in MAIN_MENU_NUMERIC1Configuration(30323)

40340

329

0x149

MAIN_MENU_NUMERIC3

NAME (32–bits)

Read/write
Memory

Displaying user-defined parameter name.


40332

331

0x14B

MAIN_MENU_NUMERIC3

PRIORITY

Read/write
Memory

Priority of the parameter for sequence of display in the main menu.

40333

332

0x14C

MAIN_MENU_NUMERIC3

CONFIGURATION

Read/write
Memory

See the table in MAIN_MENU_NUMERIC1Configuration(30323)

40054

53

0x35

MAIN_MENU_NUMERIC4

PRESENTVALUE

Read/write
Memory

Present value of the parameter.

40335

334

0x14E

MAIN_MENU_NUMERIC4

NAME (32–bits)

Read/write
Memory

Displaying user-defined parameter name.


40337

336

0x150

MAIN_MENU_NUMERIC4

PRIORITY

Read/write
Memory

Priority of the parameter for sequence of display in the main menu.

40338

337

0x151

MAIN_MENU_NUMERIC4

CONFIGURATION

Read/write
Memory

See the table in MAIN_MENU_NUMERIC1Configuration(30323)

40055

54

0x36

MAIN_MENU_NUMERIC5

PRESENTVALUE

Read/write
Memory

Present value of the parameter

40340

339

0x153

MAIN_MENU_NUMERIC5

NAME (32–bits)

Read/write
Memory

Displayed user-defined parameter name.


40342

341

0x155

MAIN_MENU_NUMERIC5

PRIORITY

Read/write
Memory

Priority of the parameter for sequence of display in the main menu.

40343

342

0x156

MAIN_MENU_NUMERIC5

CONFIGURATION

Read/write
Memory

See the table in MAIN_MENU_NUMERIC1Configuration(30323)

40056

55

0x37

MAIN_MENU_NUMERIC6

PRESENTVALUE

Read/write
Memory

Present value of the parameter

40345

344

0x158

MAIN_MENU_NUMERIC6

NAME (32–bits)

Read/write
Memory

Displaying user-defined parameter name.


40347

346

0x15A

MAIN_MENU_NUMERIC6

PRIORITY

Read/write
Memory

Priority of the parameter for sequence of display in the main menu.

40348

347

0x15B

MAIN_MENU_NUMERIC6

CONFIGURATION

Read/write
Memory

See the table in MAIN_MENU_NUMERIC1Configuration(30323)

40350

349

0x15D

MAIN_MENU_NUMERIC7

NAME (32–bits)

Read/write
Memory

Displaying user-defined parameter name.


40057

56

0x38

MAIN_MENU_NUMERIC7

PRESENTVALUE

Read/write
Memory

Present value of the parameter.

40352

351

0x15E

MAIN_MENU_NUMERIC7

PRIORITY

Read/write
Memory

Priority of the parameter for sequence of display in the main menu.

40353

352

0x15F

MAIN_MENU_NUMERIC7

CONFIGURATION

Read/write
Memory

See the table in MAIN_MENU_NUMERIC1Configuration(30323)

40058

57

0x39

MAIN_MENU_NUMERIC8

PRESENTVALUE

Read/write
Memory

Present value of the parameter.

40355

354

0x162

MAIN_MENU_NUMERIC8

NAME (32–bits)

Read/write
Memory

Displaying user-defined parameter name.


40357

356

0x164

MAIN_MENU_NUMERIC8

PRIORITY

Read/write
Memory

Priority of the parameter for sequence of display in the main menu.

40358

357

0x165

MAIN_MENU_NUMERIC8

CONFIGURATION

Read/write
Memory

See the table in MAIN_MENU_NUMERIC1Configuration(30323)

40107

106

0x6A

MAIN_MENU_BOOLEAN

ALLPRESENTVALUES

Read/write
Memory

Bit

Name

0

1

0

Boolean1PresentValue

Not active(def)

Active

1

Boolean2PresentValue

Not active(def)

Active

6

Boolean7PresentValue

Not active(def)

Active

7

Boolean8PresentValue

Not active(def)

Active

40114

113

0x71

MAIN_MENU_BOOLEAN1

PRESENTVALUE

Read/write
Memory

Present value of the parameter.

40360

359

0x167

MAIN_MENU_BOOLEAN1

NAME (32–bits)

Read/write
Memory

Displaying user-defined parameter name.


40362

361

0x169

MAIN_MENU_BOOLEAN1

TRUETEXT (32–bits)

Read/write
Memory

Text for the parameter’s true value.


40364

363

0x16B

MAIN_MENU_BOOLEAN1

FALSETEXT (32–bits)

Read/write
Memory

Text for the parameter’s false value.


40366

365

0x16D

MAIN_MENU_BOOLEAN1

PRIORITY

Read/write
Memory

Priority of the parameter for sequence of display in the main menu.

40367

366

0x16E

MAIN_MENU_BOOLEAN1

CONFIGURATION

Read/write
Memory

Bit

Name

0

1

0

Active

Not active(def)

Active

40115

114

0x72

MAIN_MENU_BOOLEAN2

PRESENTVALUE

Read/write
Memory

Present value of the parameter.

40369

368

0x170

MAIN_MENU_BOOLEAN2

NAME (32–bits)

Read/write
Memory

Displaying user-defined parameter name.


40371

370

0x172

MAIN_MENU_BOOLEAN2

TRUETEXT (32–bits)

Read/write
Memory

Text for the parameter’s true value.


40373

372

0x174

MAIN_MENU_BOOLEAN2

FALSETEXT (32–bits)

Read/write
Memory

Text for the parameter’s false value.


40375

374

0x176

MAIN_MENU_BOOLEAN2

PRIORITY

Read/write
Memory

Priority of the parameter for sequence of display in the main menu.

40376

375

0x177

MAIN_MENU_BOOLEAN2

CONFIGURATION

Read/write
Memory

Bit

Name

0

1

0

Active

Not active(def)

Active

40116

115

0x73

MAIN_MENU_BOOLEAN3

PRESENTVALUE

Read/write
Memory

Present value of the parameter.

40378

377

0x179

MAIN_MENU_BOOLEAN3

NAME (32–bits)

Read/write
Memory

Displaying user-defined parameter name.


40380

379

0x17B

MAIN_MENU_BOOLEAN3

TRUETEXT (32–bits)

Read/write
Memory

Text for the parameter’s true value.


40382

381

0x17D

MAIN_MENU_BOOLEAN3

FALSETEXT (32–bits)

Read/write
Memory

Text for the parameter’s false value.


40384

383

0x17F

MAIN_MENU_BOOLEAN3

PRIORITY

Read/write
Memory

Priority of the parameter for sequence of display in the main menu.

40385

384

0x180

MAIN_MENU_BOOLEAN3

CONFIGURATION

Read/write
Memory

Bit

Name

0

1

0

Active

Not active(def)

Active

40117

116

0x74

MAIN_MENU_BOOLEAN4

PRESENTVALUE

Read/write
Memory

Present value of the parameter.

40387

386

0x182

MAIN_MENU_BOOLEAN4

NAME (32–bits)

Read/write
Memory

Displaying user-defined parameter name.


40389

388

0x184

MAIN_MENU_BOOLEAN4

TRUETEXT (32–bits)

Read/write
Memory

Text for the parameter’s true value.


40391

390

0x186

MAIN_MENU_BOOLEAN4

FALSETEXT (32–bits)

Read/write
Memory

Text for the parameter’s false value.


40393

392

0x188

MAIN_MENU_BOOLEAN4

PRIORITY

Read/write
Memory

Priority of the parameter for sequence of display in the main menu.

40394

393

0x189

MAIN_MENU_BOOLEAN4

CONFIGURATION

Read/write
Memory

Bit

Name

0

1

0

Active

Not active(def)

Active

40118

117

0x75

MAIN_MENU_BOOLEAN5

PRESENTVALUE

Read/write
Memory

Present value of the parameter.

40396

395

0x18B

MAIN_MENU_BOOLEAN5

NAME (32–bits)

Read/write
Memory

Displaying user-defined parameter name.


40398

397

0x18D

MAIN_MENU_BOOLEAN5

TRUETEXT (32–bits)

Read/write
Memory

Text for the parameter’s true value.


40400

399

0x18F

MAIN_MENU_BOOLEAN5

FALSETEXT (32–bits)

Read/write
Memory

Text for the parameter’s false value.


40402

401

0x191

MAIN_MENU_BOOLEAN5

PRIORITY

Read/write
Memory

Priority of the parameter for sequence of display in the main menu.

40403

402

0x192

MAIN_MENU_BOOLEAN5

CONFIGURATION

Read/write
Memory

Bit

Name

0

1

0

Active

Not active(def)

Active

40119

118

0x76

MAIN_MENU_BOOLEAN6

PRESENTVALUE

Read/write
Memory

Present value of the parameter.

40405

404

0x194

MAIN_MENU_BOOLEAN6

NAME (32–bits)

Read/write
Memory

Displaying user-defined parameter name.


40407

406

0x196

MAIN_MENU_BOOLEAN6

TRUETEXT (32–bits)

Read/write
Memory

Text for the parameter’s true value.


40409

408

0x198

MAIN_MENU_BOOLEAN6

FALSETEXT (32–bits)

Read/write
Memory

Text for the parameter’s false value.


40411

410

0x19A

MAIN_MENU_BOOLEAN6

PRIORITY

Read/write
Memory

Priority of the parameter for sequence of display in the main menu.

40412

411

0x19B

MAIN_MENU_BOOLEAN6

CONFIGURATION

Read/write
Memory

Bit

Name

0

1

0

Active

Not active(def)

Active

40120

119

0x77

MAIN_MENU_BOOLEAN7

PRESENTVALUE

Read/write
Memory

Present value of the parameter.

40414

413

0x19D

MAIN_MENU_BOOLEAN7

NAME (32–bits)

Read/write
Memory

Displaying user-defined parameter name.


40416

415

0x19F

MAIN_MENU_BOOLEAN7

TRUETEXT (32–bits)

Read/write
Memory

Text for the parameter’s true value.


40418

417

0x1A1

MAIN_MENU_BOOLEAN7

FALSETEXT (32–bits)

Read/write
Memory

Text for the parameter’s false value.


40420

419

0x1A3

MAIN_MENU_BOOLEAN7

PRIORITY

Read/write
Memory

Priority of the parameter for sequence of display in the main menu.

40421

420

0x1A4

MAIN_MENU_BOOLEAN7

CONFIGURATION

Read/write
Memory

Bit

Name

0

1

0

Active

Not active(def)

Active

40121

120

0x78

MAIN_MENU_BOOLEAN8

PRESENTVALUE

Read/write
Memory

Present value of the parameter.

40423

422

0x1A6

MAIN_MENU_BOOLEAN8

NAME (32–bits)

Read/write
Memory

Displaying user-defined parameter name.


40425

424

0x1A8

MAIN_MENU_BOOLEAN8

TRUETEXT (32–bits)

Read/write
Memory

Text for the parameter’s true value.


40427

426

0x1AA

MAIN_MENU_BOOLEAN8

FALSETEXT (32–bits)

Read/write
Memory

Text for the parameter’s false value.


40429

428

0x1AC

MAIN_MENU_BOOLEAN8

PRIORITY

Read/write
Memory

Priority of the parameter for sequence of display in the main menu.

40440

429

0x1AD

MAIN_MENU_BOOLEAN8

CONFIGURATION

Read/write
Memory

Bit

Name

0

1

0

Active

Not active(def)

Active