Skip to main content
Skip table of contents

iSMA Configurator User Manual

Introduction

This user manual outlines the features of the iSMA Configurator software.

Revision History

Rev.DateDescription
1.021 Dec 2017First edition
1.131 Mar 2020Company data update
1.221 Apr 2022Rebranded
1.317 May 2022Corrections in section 2
Revision history

General Purpose of iSMA Configurator Software

The iSMA Configurator software is designed to perform configuration, firmware update, and diagnosis of the non-programmable iSMA devices. The iSMA Configurator can communicate with configurable modules via RS485, TCP/IP, or USB COM Port. The software is free and can be obtained from your distribution partner or downloaded from the Download Center at ismacontrolli.com.

The iSMA Configurator allows for the following actions:

  • downloading the latest firmware versions to your PC from iSMA CONTROLLI server;
  • uploading new firmware on devices;
  • creating/saving/loading the list of discovered devices (Project);
  • resetting devices;
  • reloading device settings;
  • restoring device configurations to default settings;
  • configuring devices;
  • changing or viewing communication parameters of the devices;
  • discovering gateway devices.

The iSMA Configurator allows for five types of communication:

  • Modbus RTU with the RS485 port;
  • Modbus TCP/IP with the IP port;
  • BACnet MS/TP with the RS485 port;
  • BACnet IP with the IP port;
  • USB with the direct USB cable connection.

Information about the type of communication, firmware upgrade, and configuration possibilities is described in the tables below.

Device

Firmware Update

Modbus RTU

Modbus TCP/IP

BACnet MS/TP

BACnet IP

USB

MIX Series

(Only via a gateway device)

(From FW 6.0 and HW 2.0)

X

MIX-IP Series

(From FW 6.0)

(From FW 6.0)

MINI Series

(Only via a gateway device)

(From FW 6.0)

X

MINI-IP Series

(From FW 6.0)

(From FW 6.0)

FCU

X

X

X

X

X

LP

(Only via a gateway device)

X

2D1B

(Only via a gateway device)

X

X

2D

(Only via a gateway device)

X

X

AAC20

X

X

X

X

X

AAC20-LCD

X

X

X

X

X

W0202

(Only via a gateway device)

X

X

MG-IP

X

X

Touch Point

(Only via a gateway device)

XX
Firmware updates in the iSMA Configurator

Device

Configuration

Modbus RTU

Modbus TCP/IP

BACnet MS/TP

BACnet IP

USB

MIX Series

(Only via a gateway device)

(Completely from FW 6.0)

(Completely from FW 6.0)

MIX-IP Series

X

X

(From FW 6.0)

MINI Series

(Only via a gateway device)

(From FW 6.0)

(From FW 6.0)

MINI-IP Series

X

X

(From FW 6.0)

FCU

(Only via a gateway device)

X

LP

(Only via a gateway device)

(Read-only)

X

2D1B

(Only via a gateway device)

X

X

2D

(Only via a gateway device)

X

X

AAC20

X

X

AAC20-LCD

X

X

W0202

(Only via a gateway device)

X

X

MG-IP

X

X

X

Touch Point

(Only via a gateway device)

XX
Configuration options in the iSMA Configurator
JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.