Skip to main content
Skip table of contents

List of Modbus Registers


Modbus Address

Decimal Address

Hex Address

Register Name

Access

Description

40001

0

0x00

VERSION AND TYPE

Read-only

Controller firmware version and type

40002

1

0x01

HARDWARE VERSION

Read-only

Controller Hardware version

40003

2

0x02

MODBUS ADDRESS

Read&write

Memory

Controller Modbus TCP/IP slave address

40004

3

0x03

UPTIME_LO

Read-only


40005

4

0x04

UPTIME_HI

Read-only


40008

7

0x07

COM2_STEADY_TIME

Read & Write

Memory


40009

8

0x08

RS485  BAUD RATE

Read&write

Memory

Transmission baud rate is defined by the user calculated using the formula:

The default value is 11520 (115200 bps)

40010

9

0x09

RS485  STOP BITS

Read&write

Memory

Supported values are 1 and 2

The default value is 1

40011

10

0x0A

RS485 DATA BITS

Read&write

Memory

Supported values are 7 and 8

The default value is 7

40012

11

0x0B

RS485 PARITY BIT

Read&write

Memory

The default value is 0 (no parity)

Allowed values:

Value

Description

0 (default)

none

1

Odd

2

Even

3

Always 1

4

Always 0

40014

13

0x0D

RS485
 MODBUS PROTOCOL TYPE

Read&write

Memory

Protocol Type (40014)
0 – RTU, 1 – ASCII
The default value is 0 - RTU.

40016

15

0x0F

STATE OF DIGITAL INPUTS

Read-only

State of digital inputs

40017

16

0x10

STATE OF UNIVERSAL INPUTS

WORKING AS DIGITAL INPUTS

Read-only

Status of universal inputs working as digital inputs

40018

17

0x11

STATE OF DIGITAL OUTPUTS

Read&write

Memory

State of digital outputs

40019

18

0x12

STATE OF ANALOG OUTPUTS

WORKING AS DIGITAL OUTPUTS

Read&write

Memory

State of analog outputs working as digital outputs

40022

21

0x15

COUNTER RESET

Read&write

Memory

Set bit in register to reset corresponding counter.

40023

22

0x16

COUNTER 1 LSB

Read&write

Memory

32-bit counters for each digital input counting pulses.

40024

23

0x17

COUNTER 1 MSB



40025

24

0x18

COUNTER 2 LSB

Read&write

Memory


40026

25

0x19

COUNTER 2 MSB



40027

26

0x1A

COUNTER 3 LSB

Read&write

Memory


40028

27

0x1B

COUNTER 3 MSB



40029

28

0x1C

COUNTER 4 LSB

Read&write

Memory


40030

29

0x1D

COUNTER 4 MSB



40046

45

0x2D

COUNTER 12 MSB



40071

70

0x46

UNIVERSAL INPUT VOLTAGE 1

Read-only

Voltage measurement value is expressed in mV.

Formula for the current measurements: I=U/200

where: U – register value,

200 – value of attached resistor

Temperature is expressed in Celsius degrees * 10

For a result, divide the registry value by 10.

Selection of the type sensor is done using UNIVERSAL INPUT CONFIGURATION register from 40151 to 40158 for each input separately

40072

71

0x47

UNIVERSAL INPUT TEMPERATURE 1

Read-only


40073

72

0x48

UNIVERSAL INPUT VOLTAGE 2

Read-only


40074

73

0x49

UNIVERSAL INPUT TEMPERATURE 2

Read-only


40075

74

0x4A

UNIVERSAL INPUT VOLTAGE 3

Read-only


40076

75

0x4B

UNIVERSAL INPUT TEMPERATURE 3

Read-only


40077

76

0x4C

UNIVERSAL INPUT VOLTAGE 4

Read-only


40078

77

0x4D

UNIVERSAL INPUT TEMPERATURE 4

Read-only


40079

78

0x4E

UNIVERSAL INPUT VOLTAGE 5

Read-only


40080

79

0x4F

UNIVERSAL INPUT TEMPERATURE 5

Read-only


40081

80

0x50

UNIVERSAL INPUT VOLTAGE 6

Read-only


40082

81

0x51

UNIVERSAL INPUT TEMPERATURE 6

Read-only


40083

82

0x52

UNIVERSAL INPUT VOLTAGE 7

Read-only


40084

83

0x53

UNIVERSAL INPUT TEMPERATURE 7

Read-only


40085

84

0x54

UNIVERSAL INPUT VOLTAGE 8

Read-only


40086

85

0x55

UNIVERSAL INPUT TEMPERATURE 8

Read-only


40087

86

0x56

UNIVERSAL INPUT VOLTAGE 1

Read-only


40088

87

0x57

UNIVERSAL INPUT VOLTAGE 2

Read-only


40089

88

0x58

UNIVERSAL INPUT VOLTAGE 3

Read-only


40090

89

0x59

UNIVERSAL INPUT VOLTAGE 4

Read-only


40091

90

0x5A

UNIVERSAL INPUT VOLTAGE 5

Read-only


40092

91

0x5B

UNIVERSAL INPUT VOLTAGE 6

Read-only


40093

92

0x5C

UNIVERSAL INPUT VOLTAGE 7

Read-only


40094

93

0x5D

UNIVERSAL INPUT VOLTAGE 8

Read-only


40095

94

0x5E

UNIVERSAL INPUT TEMPERATURE 1

Read-only


40096

95

0x5F

UNIVERSAL INPUT TEMPERATURE 2

Read-only


40097

96

0x60

UNIVERSAL INPUT TEMPERATURE 3

Read-only


40098

97

0x61

UNIVERSAL INPUT TEMPERATURE 4

Read-only


40099

98

0x62

UNIVERSAL INPUT TEMPERATURE 5

Read-only


40100

99

0x63

UNIVERSAL INPUT TEMPERATURE 6

Read-only


40101

100

0x64

UNIVERSAL INPUT TEMPERATURE 7

Read-only


40102

101

0x65

UNIVERSAL INPUT TEMPERATURE 8

Read-only


40103

102

0x66

RESISTIVE INPUT 1 LSB

Read-only

Resistance measurement result expressed in Ω.

Value range from 0 Ω  to 1 000 000 Ω.

Note: In PT1000 or NI1000 input working type the reading accuracy increase and the register value is multiply by 10

40104

103

0x67

RESISTIVE INPUT 1 MSB

Read-only


40105

104

0x68

RESISTIVE INPUT 2 LSB

Read-only


40106

105

0x69

RESISTIVE INPUT 2 MSB

Read-only


40107

106

0x6A

RESISTIVE INPUT 3 LSB

Read-only


40108

107

0x6B

RESISTIVE INPUT 3 MSB

Read-only


40109

108

0x6C

RESISTIVE INPUT 4 LSB

Read-only


40110

109

0x6D

RESISTIVE INPUT 4 MSB

Read-only


40111

110

0x6E

RESISTIVE INPUT 5 LSB

Read-only


40112

111

0x6F

RESISTIVE INPUT 5 MSB

Read-only


40113

112

0x70

RESISTIVE INPUT 6 LSB

Read-only


40114

113

0x71

RESISTIVE INPUT 6 MSB

Read-only


40115

114

0x72

RESISTIVE INPUT 7 LSB

Read-only


40116

115

0x73

RESISTIVE INPUT 7 MSB

Read-only


40117

116

0x74

RESISTIVE INPUT 8 LSB

Read-only


40118

117

0x75

RESISTIVE INPUT 8 MSB

Read-only


40121

120

0x78

VALUE OF ANALOG OUTPUT 1

Read&write

The voltage at the analog outputs are given in the mV range from 0 to 10000 mV

40122

121

0x79

VALUE OF ANALOG OUTPUT 2

Read&write


40123

122

0x7A

VALUE OF ANALOG OUTPUT 3

Read&write


40124

123

0x7B

VALUE OF ANALOG OUTPUT 4

Read&write


40125

124

0x7C

VALUE OF ANALOG OUTPUT 5

Read&write


40126

125

0x7D

VALUE OF ANALOG OUTPUT 6

Read&write


40134

133

0x85

BACNET_DEVICE_ID_LO

Read & Write

Memory


40135

134

0x86

BACNET_DEVICE_ID_HI

Read & Write

Memory


40136

135

0x87

COM1_BAUD_RATE

Read & Write

Memory


40137

136

0x88

COM1_STOP_BITS

Read & Write

Memory


40138

137

0x89

COM1_DATA_BITS

Read & Write

Memory


40139

138

0x8A

COM1_PARITY_BITS

Read & Write

Memory


40140

139

0x8B

COM1_RESPONSE_DELAY

Read & Write

Memory


40141

140

0x8C

WATCHDOG TIME

Read&write

Memory

Time in second before watchdog reset in case no transmission. A 0 value disables watchdog. The default value is 0 s.

40143

142

0x8E

DEFAULT STATE OF DIGITAL OUTPUTS

Read&write

Memory

State of digital outputs assigned at the start of the module and watchdog reset. The default value is 0.


40144

143

0x8F

DEFAULT STATE OF ANALOG OUTPUTS (DIGITAL)

Read&write

Memory

State of analog outputs assigned at the start of the module and watchdog reset. The default value is 0.

40145

144

0x90

DEFAULT STATE OF ANALOG OUTPUT 1

Read&write

Memory

In the registers is stored value in mV of voltage that appears at the analog output after power on or watchdog reset. The default value is 0.

40146

145

0x91

DEFAULT STATE OF ANALOG OUTPUT 2

Read&write

Memory


40147

146

0x92

DEFAULT STATE OF ANALOG OUTPUT 3

Read&write

Memory


40148

147

0x93

DEFAULT STATE OF ANALOG OUTPUT 4

Read&write

Memory


40149

148

0x94

DEFAULT STATE OF ANALOG OUTPUT 5

Read&write

Memory


40150

149

0x95

DEFAULT STATE OF ANALOG OUTPUT 6

Read&write

Memory


40151

150

0x96

UNIVERSAL INPUT 1 CONFIGURATION

Read&write

Memory

Configuration of universal input and type of temperature sensor.

The default value is 1.

Value

Description / Sensor

0

Resistance measurement off

1

10K3A1 NTC

2

10K4A1 NTC

3

10K NTC Carel

4

20K6A1 NTC

5

2,2K3A1 NTC B=3975K

6

3K3A1 NTC

7

30K6A1 NTC

8

SIE1

9

TAC1

10

SAT1

16

Pt1000

17

Ni1000

+128

Voltage measurement off

40152

151

0x97

UNIVERSAL INPUT 2 CONFIGURATION

Read&write

Memory


40153

152

0x98

UNIVERSAL INPUT 3 CONFIGURATION

Read&write

Memory


40154

153

0x99

UNIVERSAL INPUT 4 CONFIGURATION

Read&write
Memory


40155

154

0x9A

UNIVERSAL INPUT 5 CONFIGURATION

Read&write

Memory


40156

155

0x9B

UNIVERSAL INPUT 6 CONFIGURATION

Read&write

Memory


40157

156

0x9C

UNIVERSAL INPUT 7 CONFIGURATION

Read&write

Memory


40158

157

0x9D

UNIVERSAL INPUT 8 CONFIGURATION

Read&write

Memory


40159

158

0x9E

FILTER TIME CONSTANT

OF THE UNIVERSAL INPUT 1

Read&write

Memory

Filter time constant, expressed in seconds in the range from 0 to 60 seconds. A value of 0 disables the filter. The default value is 2 s.

Filter time constant, expressed in seconds in the range from 0 to 60 seconds. A value of 0 disables the filter. The default value is 2 s.

40160

159

0x9F

FILTER TIME CONSTANT

OF THE UNIVERSAL INPUT 2

Read&write

Memory



40161

160

0xA0

FILTER TIME CONSTANT

OF THE UNIVERSAL INPUT 3

Read&write

Memory


40162

161

0xA1

FILTER TIME CONSTANT

OF THE UNIVERSAL INPUT 4

Read&write

Memory


40163

162

0xA2

FILTER TIME CONSTANT

OF THE UNIVERSAL INPUT 5

Read&write

Memory


40164

163

0xA3

FILTER TIME CONSTANT

OF THE UNIVERSAL INPUT 6

Read&write

Memory


40165

164

0xA4

FILTER TIME CONSTANT

OF THE UNIVERSAL INPUT 7

Read&write

Memory


40166

165

0xA5

FILTER TIME CONSTANT

OF THE UNIVERSAL INPUT 8

Read&write

Memory


40167

166

0xA6










RESOLUTION OF THE UNIVERSAL INPUTS





Read&write

Memory

Resolution of universal inputs. When bit is set measurement at corresponding input is done with 16-bit resolution.

By default, all measurements are done with 12-bit resolution.

40168

167

0xA7

ANALOG OUTPUT 1 CONFIGURATION

Read&write

Memory

By default, all measurements are done with 12-bit resolution.

Configuring the mode of analog output according to the following table:

Value

Description

0 (default)

Voltage output 0‑10V

1

PWM 1Hz

2

PWM 10Hz

3

PWM 100Hz

4

PWM 0.1Hz

5

PWM 0.01Hz

40169

168

0xA8

ANALOG OUTPUT 2 CONFIGURATION

Read&write

Memory


40170

169

0xA9

ANALOG OUTPUT 3 CONFIGURATION

Read&write

Memory


40171

170

0xAA

ANALOG OUTPUT 4 CONFIGURATION

Read&write

Memory


40172

171

0xAB

ANALOG OUTPUT 5 CONFIGURATION

Read&write

Memory


40173

172

0xAC

ANALOG OUTPUT 6 CONFIGURATION

Read&write

Memory


List of Modbus registers
JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.