Advanced parameters of the AHU application are available directly from the iSMA Tool/iC Tool. After connecting and logging into the AAC20 controller, expand the device tree, and go to the Logic folder. In the expanded Logic folder, there are the main functional modules.

Functional modules (except Inputs, Outputs, Setpoints, Config, and General) contain the Parameters subfolder with advanced parameters allowing to tune the AHU application to the air handling unit to be controlled. Most of air handling unit types do not require changes and can remain with default values (changed only in special implementations). The parameters that may typically be needed for fine-tuning are usually loop settings, but in many cases the defaults are sufficient.

Note: Advanced parameters are available only from the iSMA Tool/iC Tool level - they are not available from the LCD, web server or via BACnet IP/Modbus TCP.

The list of available advanced parameters divided into functional modules:

Dampers

No

Name

Description

Range

Default

Units

1

MAT_MinSetpoint

Minimum mixed air temperature setpoint

0-50

10

°C

2

MAT_MaxSetpoint

Maximum mixed air temperature setpoint

0-50

15

°C

3

MAT_P_band

Mixed air temperature control P-band

0.01-100

10

100/K

4

MAD_RunTime

Actuator damper runtime - 0=disable runtime

0-1440

150

sec

5

OAT_MinSetpoint

Minimum outside air temperature

-50-50

-10

°C

6

OAT_MaxSetpoint

Maximum outside air temperature

-50-50

10

°C

7

DMS_MinPosition

Minimum damper position

0-100

20

%

8

DMS_MaxPosition

Maximum damper position

0-100

100

%

9

DMS_StartRatioControl

Ratio damper control signal sequence start

0-100

0

%

10

DMS_StopRatioControl

Ratio damper control signal sequence stop

0-100

100

%

11

DMS_RatioEnable

Ratio damper control signal enable - true=enable

False/true

False

N/a

12

DMS_RampTime

Ramp time damper control signal

1-100

10

%/min

Advanced parameters for dampers

Exchanger

No

Name

Description

Range

Default

Units

1

ERT_MinSetpoint

Exchanger temperature low setpoint

0-50

10

°C

2

ERT_MaxSetpoint

Exchanger temperature high setpoint

0-50

15

°C

3

ERT_P_band

Exchanger temperature control P-band

0.01-100

10

100/K

4

OAT_MinSetpoint

Minimum outside air temperature

-50-50

-10

°C

5

OAT_MaxSetpoint

Maximum outside air temperature

-50-50

10

°C

6

OAT_FrostProtection

Low limit frost protection

-50-50

6

°C

7

ERS_MinRecovery

Minimum exchanger control signal

0-100

0

%

8

ERS_MaxRecovery

Maximum exchanger control signal

0-100

100

%

9

ERS_StartRatioControl

Ratio exchanger control signal sequence start

0-100

0

%

10

ERS_StopRatioControl

Ratio exchanger control signal sequence stop

0-100

100

%

11

ERS_RatioEnable

Ratio exchanger control signal enable - true=enable

False/true

False

N/a

12

ERP_OffDelay

Exchanger pump switch off delay

0-3600

300

sec

13

ERP_StatusAlarmDelay

Delay status alarm - 0=disable, 1=failure, <0=fail-to-command alarm, >1=status alarm

-600-600

1

sec

14

ERP_Pmp_Vlv_Exercise

Exchanger pump / valve exercise time

0-600

120

sec

15

ERP_WheelRelease

Wheel release - false=plant mode, true=continuous

False/true

False

N/a

16

ERP_OnDelay

Start-up delay pump / wheel

0-300

5

sec

Advanced parameters for exchangers

Preheater

No

Name

Description

Range

Default

Units

1

RWT_LowSetpoint

Return water temperature low setpoint

0-100

10

°C

2

RWT_HighSetpoint

Return water temperature high setpoint

0-100

25

°C

3

RWT_MaxSetpoint

Return water temperature maximum setpoint

0-100

85

°C

4

RWT_P_band

Return water temperature control P-band

0.01-100

10

100/K

5

DME_OnDelay

Damper enable or alarm delay - 0=alarm disable

0-3600

300

sec

6

DME_EmergencyStop

AHU stops on pump alarm at low outside air temperature - true=yes

False/true

False

N/a

7

OAT_MinSetpoint

Outside air temperature minimum value

-50-50

-10

°C

8

OAT_MaxSetpoint

Outside air temperature maximum value

-50-50

10

°C

9

OAT_FrostProtection

Low limit frost protection

-50-50

6

°C

10

FEZ_RWT_SptUp

Frost protection return water temperature setpoint raise

0-50

15

K

11

FEZ_SetupRamp

Raised setpoint decrease during frost recovery

1-20

1

K/min

12

HPU_OnDelay

Start-up delay heating pump

0-300

5

sec

13

HPU_OffDelay

Heating pump switch off delay

0-3600

300

sec

14

HPU_Enable

Heating pump enable - true=enable

False/true

True

N/a

15

HPU_Pmp_Vlv_Exercise

Heating pump and valve exercise time

0-600

120

sec

16

HPU_StatusAlarmDelay

Delay status alarm - 0=disable, 1=failure, <0=fail-to-command alarm, >1=status alarm

-600-600

1

sec

17

HTS_StartRatioControl

Ratio control signal sequence start

0-100

0

%

18

HTS_StopRatioControl

Ratio control signal sequence stop

0-100

100

%

19

HTS_RatioEnable

Ratio control enable - true=enable

False/true

False

N/a

20

HTV_FrostProt_ValveUp

Heating valve position during frost protection

0-100

100

%

21

HTV_Ramp

Heating valve raised position decrease during frost recovery

1-100

10

%/min

Advanced parameters for preheaters

Cooler

No

Name

Description

Range

Default

Units

1

OAT_CoolerLowLimit

Low limit outside air temperature - cooler valve closed

-50-50

14

°C

2

CCV_VlvRamp

Valve position increase per minute

1-100

5

%/min

3

CCV_MinVlvPos

Minimum valve position

0-100

0

%

4

CCV_MaxVlvPos

Maximum valve position

0-100

100

%

5

CCV_Vlv_Exercise

Cooling valve exercise time - 0=disable

0-600

120

sec

6

CCS_StartRatioControl

Ratio temperature control sequence start

0-100

0

%

7

CCS_StopRatioControl

Ratio temperature control sequence stop

0-100

100

%

8

DEH_StartRatioControl

Ratio dehumidification control sequence start

0-100

0

%

9

DEH_StopRatioControl

Ratio dehumidification control sequence stop

0-100

100

%

10

CCS_RatioEnable

Ratio temperature control enable - true=enable

False/true

False

N/a

11

DEH_RatioEnable

Ratio dehumidification control enable - true=enable

False/true

False

N/a

12

CCV_CoolOnHumDisable

Disable cooling on humidify - true=yes

False/true

True

N/a

13

LIM_Setpoint

Low limit setpoint

0-50

14

°C

14

LIM_P_band

Low limit P-band

0.01-100

10

100/K

15

LIM_I_time

Low limit I-time

0-1000

0

100/sec

Advanced parameters for coolers

Reheater

No

Name

Description

Range

Default

Units

1

OAT_FrostProtection

Low limit frost protection

-50-50

6

°C

2

HPU_OnDelay

Start-up delay heating pump

0-300

5

sec

3

HPU_OffDelay

Heating pump switch off delay

0-3600

300

sec

4

HPU_Enable

Heating pump enable - true=enable

False/true

True

N/a

5

HPU_Pmp_Vlv_Exercise

Heating pump and valve exercise time

0-600

120

sec

6

HPU_StatusAlarmDelay

Delay status alarm - 0=disable, 1=failure, <0=fail-to-command alarm, >1=status alarm

-600-600

1

sec

7

HTS_StartRatioControl

Ratio control signal sequence start

0-100

0

%

8

HTS_StopRatioControl

Ratio control signal sequence stop

0-100

100

%

9

HTS_RatioEnable

Ratio control enable - true=enable

False/true

False

N/a

10

HTV_FrostProt_ValveUp

Heating valve position during frost protection

0-100

100

%

11

HTV_Ramp

Heating valve raised position decrease during frost recovery

0-100

10

%/min

Advanced parameters for reheaters

Fans

No

Name

Description

Range

Default

Units

1

FDP_BeltAlarmDelay

Delay fan belt alarm - 0=disable

0-600

120

sec

2

FSC_OffOnDelay

Delay fan start/stop

0-600

5

sec

3

FSC_Ramp

Control signal increase per minute

0-100

1

%/min

4

FSC_MinSignal

Minimum fan speed control signal

0-100

30

%

5

FSC_MaxSignal

Maximum fan speed control signal

0-100

100

%

6

FSC_ManualReset

Manual / automatic alarm reset - false=manual

False/true

False

N/a

7

DSP_PressSptRamp

Setpoint increase per minute

0-1000

50

Pa/min

8

DSP_PressDisP_band

Static discharge pressure control P-band

1-1000

0.5

100/Pa

9

DSP_PressRetP_band

Static return pressure control P-band

1-1000

0.5

100/Pa

10

DSP_PressDisI_time

Static discharge pressure control I-time

0-1000

0

100/sec

11

DSP_PressRetI_time

Static return pressure control I-time

0-1000

0

100/sec

12

DSP_NightReduce

Night reduction of control signal

0-100

50

%

Advanced parameters for fans

Humidifier

No

Name

Description

Range

Default

Units

1

OAT_HighHum

High limit for humidification

-50-50

14

°C

2

OAT_LowDeh

Low limit for dehumidification

-50-50

15

°C

3

RAH_MinHumSpt

Minimum room humidity setpoint during winter

0-100

30

%RH

4

RAH_MaxHumSpt

Maximum room humidity setpoint during summer

0-100

60

%RH

5

RAH_P_band

Relative room/return humidity control P-band

0.01-100

25

100/%RH

6

RAH_I_time

Relative room/return humidity control I-time

0-1000

0

100/sec

7

WC_LowOAT

Start point outside air temperature winter compensation

-50-50

-10

°C

8

WC_HighOAT

End point outside air temperature winter compensation

-50-50

10

°C

9

SC_LowOAT

Start point outside air temperature summer compensation

-50-50

20

°C

10

SC_HighOAT

End point outside air temperature summer compensation

-50-50

30

°C

11

DAH_MaxSpt

Maximum setpoint discharge air relative humidity

0-100

90

%RH

12

DAH_P_band

Maximum setpoint control P-band

0.01-100

8.33

100/%RH

13

DAH_LowAbsHumSpt

Discharge air absolute humidity low setpoint

0-25

5

g/kg

14

DAH_HighAbsHumSpt

Discharge air absolute humidity high setpoint

0-25

15

g/kg

15

HUM_P_band

Humidification control P-band

0.01-100

25

100/%RH

16

HUM_RampUp

Relative humidity control signal increase per minute

1-100

10

%/min

17

HUM_FanOnDelay

Delay after fan start

0-3600

300

sec

18

HUM_StatusAlarmDelay

Delay status alarm - 0=disable, 1=failure, <0=fail-to-command alarm, >1=status alarm

-600-600

1

sec

19

DEH_P_band

Dehumidification control P-band

0.01-100

16.67

100/%RH

20

DEH_RampUp

Relative humidity control signal increase per minute

1-100

10

%/min

21

HUMDEH_I_time

Humidify / dehumidify control I-time

0-1000

0

100/sec

22

HUMDEH_ComfZone

Comfort zone between humidify / dehumidify

0-40

4

%RH

Advanced parameters for humidifiers

Economizer

No

Name

Description

Range

Default

Units

1

AtmPressure

Atmospheric pressure

80-120

101.30

kPa

2

EnthalpyDiff

Enthalpy difference

0-20

5

kJ/kg

3

AbsHumDiff

Absolute humidity difference

0.0-5.0

1

g/kg

4

SwitchoverDel

Switch over delay

0-1800

300

sec

Advanced parameters for the economizer function

Control

No

Name

Description

Range

Default

Units

1

OAT_HeaterLimit

Limit outside air temperature - heater closed

-50-50

20

°C

2

OAT_CoolerLimit

Limit outside air temperature - cooler closed

-50-50

14

°C

3

OAT_FrostProt

Limit outside air temperature start / frost  protection

-50-50

6

°C

4

DAT_LowSetpoint

Discharge air temperature low setpoint

0-50

14

°C

5

DAT_HighSetpoint

Discharge air temperature high setpoint

0-50

26

°C

6

SC_RoomStartComp

Start point outside air temperature summer room temperature compensation

-50-50

20

°C

7

SC_RoomEndComp

End point outside air temperature summer room temperature compensation

-50-50

30

°C

8

SC_RoomSptRaise

Room temperature setpoint raise

0-10

4

K

9

RT_P_band

Room temperature control P-band

0.01-100

50

100/K

10

RT_I_time

Room temperature control I-time

0-1000

0

100/sec

11

RT_ComfortZone

Room temperature comfort zone

0-10

2

K

12

RT_DATSpt_shift

Span for discharge air temperature setpoint shift

0-100

60

%

13

RT_EnergyRecStart

Sequence start point of exchanger

0-100

0

%

14

RT_EnergyRecEnd

Sequence end point of exchanger

0-100

100

%

15

WC_DischStartComp

Start point outside air temperature winter discharge air temperature compensation

-50-50

-10

°C

16

WC_DischEndComp

End point outside air temperature winter discharge air temperature compensation

-50-50

10

°C

17

WC_DischSptRaise

Discharge air temperature setpoint  raise

0-10

4

K

18

DAT_P_band

Discharge air temperature control P-band

0.01-100

6.67

100/K

19

DAT_I_time

Discharge air temperature control I-time

0-1000

0.17

100/sec

20

DAT_HeatStart

Sequence start point of heating valve

0-100

0

%

21

DAT_HeatEnd

Sequence end point of heating valve

0-100

50

%

22

DAT_EnergyRecStart

Sequence start point of exchanger

0-100

50

%

23

DAT_EnergyRecEnd

Sequence end point of exchanger

0-100

75

%

24

DAT_CoolStart

Sequence start point of cooling valve

0-100

75

%

25

DAT_CoolEnd

Sequence end point of cooling valve

0-100

100

%

26

DAT_SptRamp

Discharge air temperature setpoint raise

0-20

1

K

27

DAT_SptDecTime

Discharge air temperature control raised setpoint decrease time

0-3600

600

sec

28

HUM_FanStart

Sequence start point of fan speed

0-100

0

%

29

HUM_FanEnd

Sequence end point of fan speed

0-100

100

%

30

DEH_DampersStart

Sequence start point dampers

0-100

0

%

31

DEH_DampersEnd

Sequence end point dampers

0-100

30

%

32

DEH_FanStart

Sequence start point of fan speed

0-100

30

%

33

DEH_FanEnd

Sequence end point of fan speed

0-100

70

%

34

DEH_CoolStart

Sequence start point of cooling valve

0-100

70

%

35

DEH_CoolEnd

Sequence end point of cooling valve

0-100

100

%

36

CO2_P_band

Air quality control P-band

0.01-100

0.5

100/ppm

37

CO2_DampersStart

Sequence start point air quality override dampers

0-100

0

%

38

CO2_DampersEnd

Sequence end point air quality override dampers

0-100

50

%

39

CO2_FanStart

Sequence start point air quality override fan speed

0-100

50

%

40

CO2_FanEnd

Sequence end point air quality override fan speed

0-100

100

%

41

MAD_RecircTimeStart

Period of forced recirculation after start

0-3600

600

sec

Advanced control parameters